Sc-6 and sc-12 output wiring, Warning, Sc outputs – LAARS SC 12 - Install and Operating Manual User Manual

Page 14: On/off units, 2 stage units, 3 stage units, 4 stage units

Advertising
background image

Page 14

LAARS Heating Systems

Additional output relays can be

ordered separately (CA002300). Each

active Stage Output must have a relay.

WARNING

This Laars Heating Systems control is strictly an operating control; it should

never be used as a primary limit or safety control. All equipment must have

its own certifi ed limit and safety controls required by local codes. The installer

must verify proper operation and correct any safety problems prior to the

installation of this Laars Heating Systems control.

SC

Outputs

Output

NO

C

Limit

Circuit

ON/OFF Units

Lo

Output

2 Stage Units

Hi

Output

NO

C

Hi

Circuit

Lo

Output

3 Stage Units

NO

C

Mid

Output

Hi

Output

Lo

Output

4 Stage Units

LoMid

Output

HiMid

Output

Hi

Output

NO

C

Limit

Circuit

NO

C

Limit

Circuit

NO

C

Mid

Circuit

NO

C

Hi

Circuit

NO

C

Limit

Circuit

NO

C

LoMid

Circuit

NO

C

HiMid

Circuit

NO

C

Hi

Circuit

SC-6 and SC-12 OUTPUT WIRING

INSTALLING THE OUTPUT RELAYS

• Each output (OUTPUT 1 through OUTPUT 12) which is to be used must have

a relay installed in the socket.

• Check the charts on pg. 17 to locate where the relays should be installed for

each particular type of installation.

• To install a relay, orient the pins and then press it gently into the appropriate socket.

• Any Stage Output which does not have a relay must have its stage switch to the OFF

position (see pg. 23).

WIRING THE STAGE OUTPUTS

• Each Stage Output has one Normally Open (N.O.) relay contact.

• The N.O. contacts are dry contacts only. They do not source any voltage.

• Each N.O. contact is capable of switching 6A resistive.

• Total output of all stages, including the SYSTEM, must not exceed 15A.

ON/OFF Units

• Each unit has one relay and one set of Stage OUTPUT contacts associated with it.

OUTPUT

OUTPUT

• Wire the N.O. relay contacts in series with the unit’s limit circuit.

2 Stage (Lo/Hi) Units

• Each unit has two OUTPUT relays associated with it.

OUTPUT

OUTPUT

• Check the chart (pg. 17) for the Lo and Hi Stage Output positions.

• Connect the Lo N.O. relay contacts in series with the unit’s limit circuit.

• Connect the Hi N.O. relay contacts to the Hi control circuit.

3 Stage (Lo/Mid/Hi) Units

• Each unit has three OUTPUT relays associated with it.

OUTPUT

OUTPUT

• Check the chart (pg. 17) for the Lo, Mid and Hi Stage Output positions.

• Connect the Lo N.O. relay contacts in series with the unit’s limit circuit.

• Connect the Mid N.O. relay contacts to the Mid control circuit.

• Connect the Hi N.O. relay contacts to the Hi control circuit.

4 Stage (Lo/LoMid/HiMid/Hi) Units

• The unit has four OUTPUT relays associated with it.

OUTPUT

OUTPUT

• Check the chart (pg. 17) for the Lo, LoMid, HiMid and Hi Stage Output positions.

• Connect the Lo N.O. relay contacts in series with the unit’s limit circuit.

• Connect the LoMid N.O. relay contacts to the LoMid control circuit.

• Connect the HiMid N.O. relay contacts to the HiMid control circuit.

• Connect the Hi N.O. relay contacts to the Hi control circuit.