Laars Sequencing Controls

DHW CALL

• When the DHW terminals are closed, the SC Set Point immediately changes to 200°F. This will happen regardless of outdoor

DHW

DHW

temperature, the status of the Setback/Shutdown inputs, or the External Set Point (if that function is being used).

• Typically, the DHW input is wired to an aquastat which monitors the domestic hot water temperature. When the aquastat calls

DHW

DHW

for heat, it will close the DHW input terminals.

DHW

DHW

• If the System Output is confi gured for Combustion Air Damper operation, the System relay output will be closed when any Stage

Output is activated to hold the 200°F set point.

• If the System Output is confi gured for System Pump operation without DHW priority (see pg. 22) then the System relay will be

closed whenever the outdoor temperature is below the Outdoor Cutoff, regardless of the DHW input status.

• If the System Output is confi gured for System Pump operation with DHW priority (see pg. 22) then:

-

The System relay output will be open for the time set by the DHW Priority time dhP

-

After the DHW priority time has elapsed, the System relay output will revert to its normal mode of operation (that is either

on or off depending on outdoor temperature.)

• For wiring the DHW input, see pg. 6.