Fuel types and pressures – Carrier 48TCA04---A12 User Manual

Page 23

Advertising
background image

23

Limit Switch
and Shield

C08284

Fig. 28 -- Limit Switch Location

Fuel Types and Pressures

Natural Gas — The 48TC unit is factory--equipped for use

with Natural Gas fuel at elevation under 2000 ft (610 m).

See section Orifice Replacement for information in

modifying this unit for installation at elevations above

2000 ft (610 m).

Gas line pressure entering the unit’s main gas valve must

be within specified ranges. Adjust unit gas regulator valve

as required or consult local gas utility.

Table 4 – Natural Gas Supply Line Pressure Ranges

UNIT MODEL

UNIT SIZE

MIN

MAX

48TC

All

4.0 in. wg

(996 Pa)

13.0 in. wg

(3240 Pa)

Manifold pressure is factory--adjusted for NG fuel use.

Adjust as required to obtain best flame characteristic.

Table 5 – Natural Gas Manifold Pressure Ranges

UNIT

MODEL

UNIT

SIZE

HIGH

FIRE

LOW

FIRE

RANGE

48TCD,S

48TCE,R

48TCF,T

All

3.5 in. wg

(872 Pa)

1.7 in. wg

(423 Pa){

2.0---5.0 in. wg (Hi)

(498---1245 Pa)

48TCL

48TCM

48TCN

All

3.5 in. wg

(872 Pa)

NA

2.0---5.0 in. wg (Hi)

(498---1245 Pa)

NA: Not Available
{

3 Phase models only

Liquid Propane — Accessory packages are available for

field--installation that will convert the 48TC unit (except

low NO

x

model) to operate with Liquid Propane (LP)

fuels. These kits include new orifice spuds, new springs

for gas valves and a supply line low pressure switch. See

section on Orifice Replacement for details on orifice size

selections.

Low NO

x

models include specially--sized orifices and use

of different flue flow limits and tube baffles. Because of

these extra features, conversion of these models to LP is

not recommended.

Fuel line pressure entering unit gas valve must remain

within specified range.

Table 6 – Liquid Propane Supply Line Pressure Ranges

UNIT MODEL

UNIT SIZE

MIN

MAX

48TCD,E,F

48TCS,R,T

All

11.0 in. wg

(2740 Pa)

13.0 in. wg

(3240 Pa)

48TCL,M,N

All

NA

NA

Manifold pressure for LP fuel use must be adjusted to

specified range. Follow instructions in the accessory kit to

make initial readjustment.

Table 7 – Liquid Propane Manifold Pressure Ranges

UNIT MODEL

UNIT SIZE

HIGH FIRE

LOW FIRE

48TCD,S

48TCE,R

48TCF,T

All

10.0 in. wg

(2490 Pa)

5.0 in. wg

(1245 Pa){

48TCL,

48TCM,

48TCN

All

NA

NA

NA: Not Available
{

3 Phase models only

Supply Pressure Switch — The LP conversion kit includes

a supply low pressure switch. The switch contacts (from

terminal C to terminal NO) will open the gas valve power

whenever the supply line pressure drops below the

setpoint. See Fig. 29 and Fig. 30. If the low pressure

remains open for 15 minutes during a call for heat, the

IGC circuit will initiate a Ignition Fault (5 flashes)

lockout. Reset of the low pressure switch is automatic on

rise in supply line pressure. Reset of the IGC requires a

recycle of unit power after the low pressure switch has

closed.

C08238

Fig. 29 -- LP Low Pressure Switch (Installed)

PNK

W2

TSTAT

GRA

BRN

IGC

J2-12

IGC

J2-11

BRN

C

NO

MGV

C

LP LPS

C08285

Fig. 30 -- LP Supply Line Low Pressure Switch Wiring