Alarm state is reset when the smoke detector alarm

condition is cleared and reset at the smoke detector in the

unit.

Connecting Discrete Inputs

Filter Status
The filter status accessory is a field--installed accessory.

This accessory detects plugged filters. When installing

this accessory, the unit must be configured for filter status

by setting MENU

Config

Inputs

input 3, 5, 8, or 9

to Filter Status and normally open (N/O) or normally

closed (N/C). Input 8 or 9 is recommended for easy of

installation. Refer to Fig. 59 and Fig. 60 for wire

terminations at J5.
Fan Status
The fan status accessory is a field--installed accessory.

This accessory detects when the indoor fan is blowing air.

When installing this accessory, the unit must be

configured

for

fan

status

by

setting

MENU

Config

Inputs

input 3, 5, 8, or 9 to Fan

Status and normally open (N/O) or normally closed (N/C).

Input 8 or 9 is recommended for easy of installation. Refer

to Fig. 59 and Fig. 60 for wire terminations at J5.
Remote Occupancy
The remote occupancy accessory is a field--installed

accessory. This accessory overrides the unoccupied mode

and puts the unit in occupied mode. When installing this

accessory, the unit must be configured for remote

occupancy by setting MENU

Config

Inputs

input 3,

5, 8, or 9 to Remote Occupancy and normally open (N/O)

or normally closed (N/C).
Also set MENU

Schedules

occupancy source to DI

on/off. Input 8 or 9 is recommended for easy of

installation. Refer to Fig. 59 and Table 21 for wire

terminations at J5.

Power Exhaust (output)

Connect the accessory Power Exhaust contactor coil(s) per

Fig. 66.

Power Exhaust

J11-3

C

THERMOSTAT

PEC

TAN

GRA

LCTB

C08464

Fig. 66 -- RTU--MP Power Exhaust Connections

Space Relative Humidity Sensor -- The RH sensor is not

used with 48TC models at this time.

Communication Wiring -- Protocols

General
Protocols are the communication languages spoken by

control devices. The main purpose of a protocol is to

communicate information in the most efficient method

possible. Different protocols exist to provide different

kinds of information for different applications. In the BAS

application, many different protocols are used, depending

on manufacturer. Protocols do not change the function of

a controller; just make the front end user different.
The RTU--MP can be set to communicate on four different

protocols: BACnet, Modbus, N2, and LonWorks. Switch 3

(SW3) on the board is used to set protocol and baud rate.

Switches 1 and 2 (SW1 and SW2) are used to set the

board’s network address. See Fig 67 for the switch setting

per protocol. The 3rd party connection to the RTU--MP is

through plug J19. Refer to the RTU--MP 3rd Party
Integration Guide
for more detailed information on

protocols, 3rd party wiring, and networking.
NOTE: Power must be cycled after changing the SW1--3
switch settings.

SW3 Protocol Selection

PROTOCOL

DS8

DS7

DS6

DS5

DS4

DS3

DS2

DS1

BACnet MS/TP

(Master)

Unused

OFF

OFF

OFF

ON

OFF

Select Baud Select Baud

Modbus

(Slave)

Unused

OFF

OFF

ON

ON

OFF

Select Baud Select Baud

N2

(Slave)

Unused

OFF

OFF

OFF

ON

ON

OFF

OFF

LonWorks

Unused

ON

ON

OFF

ON

OFF

OFF

OFF

NOTE:
DS = Dip Switch
BACnet MS/TP SW3 example shown

Baud Rate Selections

BAUD RATE

DS2

DS1

9600

OFF

OFF

19,200

ON

OFF

38,400

OFF

ON

76,800

ON

ON

C07166

Fig. 67 -- RTU--MP SW3 Dip Switch Settings

48TC