Troubleshooting flow chart – burner will not fire – Slant/Fin 3000-190 User Manual

Page 7

Advertising
background image

Yes

̈ Recheck Wiring

Is the

Limit Circuit

Closed?

YES

Does the

Control Have

Power?

NO

7

NO

NO

Is the

Red LED

(LOW WATER)

On?

The Control is

Sensing

Low Water.

CAUTION – ALWAYS ALLOW A BOILER TO COOL BEFORE ADDING WATER

The burner will not fire until the low water condition is satisfied.

̈ Check that the system is filled with water.
̈ Check that the sensor is inserted correctly into well.

Note: The use of heat-conductive grease may interfere with the

contact between the spring clip and the copper well tube.

̈ Check that the control is tightly clamped to the well.

Is the

Yellow LED

(HI TEMP)

On?

The Control is

Sensing High

Temperature.

If both the red and yellow LEDs are off and

there is a call to fire the burner, the Limit

Contacts should be closed.

Replace

Control

The burner will not fire until the boiler water has dropped to the

high limit differential set-point (10° below high limit setting).

̈ Check that the high temperature setting is correct.

Troubleshooting Flow Chart – Burner Will Not Fire

YES

YES

NO

Is the

Yellow LED

(TARGET)

On?

The Boiler has

Reached the

Target

Temperature.

When the ECONOMY function is active, the control monitors heating

demand and establishes Target boiler temperatures below the high

limit setting to conserve fuel (see “How Thermal Targeting Works”

on page 5). The burner will not fire until the boiler temperature

drops to the Target Temp Differential (see “Differentials” on page 5).

YES

Is the

PURGE

LED On?

The Control is

Purging Latent

Heat from the

Boiler.

The Thermal Pre-Purge feature holds off the burner until the

circulator has purged the boiler temperature down to 135°F.

See Purge on page 5.

YES

NO

NO

̈ Recheck Wiring