Specifications, Dimensions electro-wells, Maintenance – Slant/Fin 3000-190 User Manual

Page 8

Advertising
background image

8

83 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 •

www.hydrolevel.com

SPECIFICATIONS

FUEL SMART HYDROSTAT

MODEL 3000 and MODEL 3000-190

DIMENSIONS

ELECTRO-WELLS

LIMITED MANUFACTURERʼS WARRANTY

We warrant products manufactured by Hydrolevel Company to be free from defects in

material and workmanship for a period of two years from the date of manufacture or

one year from the date of installation, whichever occurs first. In the event of any claim

under this warranty or otherwise with respect to our products which is made within

such period, we will, at our option, repair or replace such products or refund the pur-

chase price paid to us by you for such products. In no event shall Hydrolevel Company

be liable for any other loss or damage, whether direct, indirect, incidental or conse-

quential. This warranty is your EXCLUSIVE remedy and shall be IN PLACE OF any other

warranty or guarantee, express or implied, including, without limitation, any warranty

of MERCHANTABILITY or fitness for a particular purpose. This warranty may not be

assigned or transferred and any unauthorized transfer or assignment thereof shall be

void and of no force or effect.

Input voltage

24 VAC, 60 HZ

Burner contacts

50 VA@24 VAC Pilot Duty

Ambient temperature

Room

Operating range–low limit

Off or 110°F (43°C) - 200°F (93°C)

Operating range–high limit Model 3000: 100°F (38°C) - 220°F (104°C)

Model 3000-190: 100°F (38°C) - 190°F (88°C)

MAINTENANCE

Remove the Electro-Well from the heating system every five years and clean any scale or sediment deposits from all parts that

are exposed to the boiler water. After cleaning, reinstall the well using pipe sealing compound. Teflon tape is not recommended.