A warning – Carrier 58PAV User Manual

Page 7

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

------- FIELD 24-VOLT WIRING
------- FIELD 115-, 208/230-, 460-VOLT WIRING
------- FACTORY 24-VOLT WIRING
------- FACTORY 115-VOLT WIRING

FOUR

WIRE

"?GND

115-VOLT FIELD-

SUPPLIED

FUSED

DISCONNECT

THERMOSTAT
TERMINALS

FIELD-SUPPLIED
FUSED DISCONNECT

q

y.

q

^ GND

(s>'

AUXILIARY
J-BOX

CONTROL

BOX

24-VOLT

TERMINAL

BLOCK

«HH»—-Æn*-»-

FURNACE

■ T W O

WIRE

NOTE: Connect Y-terminal as

shown for proper
operation.

208/230- OR
460-VOLT

THREE

PHASE

208/230-
VOLT
SINGLE

PHASE•

NOTE: If any of the original wire,

as supplied, must be replaced, use
same type or equivalent wire.

A78461

Fig. 8—Heating and Cooling Application Wiring Diagram

Table 5—Electrical Data

UNIT SIZE

VOLTS-

HERTZ—

PHASE

OPERATING

VOLTAGE RANGE

MAX

UNIT

AMPS

MIN

WIRE

GAGE

MAX WIRE

LENGTH (FT)t

MAX FUSE OR

HACR-TYPE

CKT BKR AMPSt

Max*

Min*

045-08

115—60—1

127

104

6.0

14

47

15

045-12

115—60—1

127

104

8.3

14

34

15

070-08

115—60—1

127

104

5.9

14

47

15

070-12

115—60—1

127

104

8.7

14

32

15

090-14

115—60—1

127

104

9.0

14

31

15

090-16

115—60—1

127

104

10.4

14

27

15

111-12

115—60—1

127

104

8.0

14

35

15

111-16

115—60—1

127

104

10.1

14

28

15

111-20

115—60—1

127

104

14.4

12

31

20

135-16

115—60—1

127

104

10.1

14

28

15

135-20

115—60—1

127

104

13.3

12

33

20

155-20

115—60—1

127

104

14.0

12

31

20

* Permissible limits of the voltage range at which the unit operates satisfactorily,

t Time-delay fuse is recommended.
t Length shown is as measured 1 way along wire path between unit and service

A WARNING

The cabinet MUST have an uninterrupted or unbroken ground
according to National Electrical Code, ANSI/ NFPA 70-1993
and Canadian Electrical Code, CSA C22.1 or local codes to
minimize personal injury if an electrical fault should occur.
This may consist of electrical wire or conduit approved for
electrical ground when installed in accordance with existing
electrical codes. Do not use gas piping as an electrical ground.

The auxiliary junction box can be moved to the right-hand side of
the furnace when a right side power supply is desired. Remove the
2 screws holding the auxiliary junction box. Mount the junction
box on the right-hand side of the furnace (holes have been
predrilled in casing). The blower door interlock switch must also
be moved to the right side of the furnace due to the length of the
wiring harness. When moved, tuck the wiring harness behind the
clip provided to keep extra wire lengths out of the way,

NOTE:

Proper polarity must be maintained for 115-v wiring. If

polarity is incorrect, the microprocessor shuts off gas flow shortly
after the completion of ignition trial period.

panel for maximum 2 percent voltage drop.

24-V WIRING — Make field 24-v connections at the 24-v
terminal strip. (See Fig. 9.) Connect terminal Y as shown in Fig. 8
for proper cooling operation. Use only AWG No. 18, color coded
copper thermostat wire.

The 24-v circuit contains an automotive-type, 3-amp fuse located
on the main control board. Any direct shorts during installation,
service, or maintenance could cause this fuse to blow. If fuse
replacement is required, use ONLY a 3-amp fuse of identical size.

ACCESSORIES

1. Electronic air cleaner (EAC)

Two screw terminals (EAC-1 and EAC-2) are provided for
EAC connection. The terminals are energized with 115-v,

1-amp maximum during blower motor operation.

2. Humidifier (HUM)

Screw terminals (HUM-1 and C) are provided for 24-v
humidifier connection. The terminals are energized with 24-v,
0.5-amp maximum during heating blower motor operation.

Step 7— Venting

Refer to the enclosed Installation Instructions, GAMA Venting
Tables for Category I Furnaces, and QUIK’VENT™ Tables for

Advertising