Installation Instructions (cont’d)

AWARNING

A gas water heater cannot operate property without the cor*

rect amount of air for combustion. Do not install in a confined
area such a closet, unless you provide air as shown in the
“Locating The New Water Heater“ section. Never obstruct
the flow of ventilation air. If you have any doubts or questions at
all, call your gas company. Failure to provide the proper
amount of combustion air can result in a fire or explosion and
can cause death, serious bodily injury, or property damage.

AWARNING

If this water heater will be used in beauty shops, barber shops,
cleaning establishments, or self-service laundries with dry
cleaning equipment, it is imperative that the water heater or
water heaters be installed so that combustion and ventilation
air be taken from outside these areas. Refer to the “Locating
The New Witer Heater” section of this manual and also the

latest edition of the National Fuel Gas Code, ANSI Z123.I, also
referred to as NFPA 54 for specifics provided concerning air
required.

Combustion Air and Ventilation

When determining the installation location for a power vent
water heater, snow accumulation and drifting should be consid­
ered in areas where applicable.

VENTING CLEARANCES

# 0" clearance for 3" PVC, ABS or CPVC Schedule 40 vent piping

from combustible surfaces.

# 18" minimum in all directions from any obstruction that may inter­

fere.

# 12" minimum from the ground, 18" ceiling overhangs. Figure 2.
# The Power Vent outlet terminal shall terminate at least 3 feet above

any forced air inlet located within 10 feet. Figure 3a.

# The Power Vent outlet terminal shall terminate at least 4 feet below,

4 feet horizontally from or 1 foot above any door, window or gravity
air inlet into the building. Figure 3a.

# 18" minimum from other gravity or natural appliance outlet vents

when direcdy above or 135° to either side of center line. Figure 3b.

36” minimum from any outlet vents when directly below or 45° to

# either side of center line. Figure 3b.

36" minimum in all directions from any other forced air appliance

# outlet vent. Figure 3b.

The location selection must provide clearances for servicing and

# proper operation of the water neater. Figure 4,

Vent termination must not be within 4 feet of any items such as gas

# meters, gas valves or other gas regulating equipment.

AWARNING

Vent termination must not be within 4 feet of any items such as
gas meters, gas valves or other gas regulating equipment.

AWARNING

Failure to have required clearances between water heater and

combustible material will result in a fire hazard.

18

** min. from

any overhang

Rue

Figure 2

Must maintain

adequate service
and maintenance
accessibility.

Figure 4

Range of degrees
avallóle for vent
pipe installation.

10