Installation Instructions (cont’d)

Gas Piping

AWARNING

Make sure the gas supplied is the same type listed on the
model rating plate. The inlet gas pressure must not exceed

14 inches water column

'A

pound per square inch (3.5kPa)].

The minimum inlet gas pressure listed on the mo^l rating
plate is for the purpose of input adjustment

AWARNING

If the gas control valve is subjected to pressures ecceeding

'A

pound per square inch (3.5kPa), the dam^ to the gas con­
trol valw could result in a fire or explosion ^m leaking gas.

AWARNING

If the main gas line shutoff serving all gas appliances is used,
also turn “oir' the gas at each appliance. Lem ^1 gas appli­
ances shut off until & water heater installation is complete.

A gas line of sufficient size must be run to the water heater.

Consult the latest edition of National Fuel Gas Code ANSI
Z223.1, also referred to as NFPA54 and the gas company con­
cerning pipe size.

There must be:

•A readily accessible manual shut off valve in the gas supply line

serving the water heater, and

•A drip leg (sediment trap) ahead of the gas control valve to help

prevent dirt and foreign materials from entering the gas control

valve.

•A flexible gas connector or a ground joint union between the

shutoff valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the

water heater. Use a soapy water solution, not a match or open

flame. Rinse off soapy solution and wipe dry.

Standard Modeb are for installation up to 3,300 feet above sea
level.
Hig;h Altitude Models are for installation from 3,300 to 5,500

feet above sea level.
If a standard model is installed above 3,300 feet or a high altitude
model is installed above 5,500 feet, the input rating must be
reduced at the rate of 4 percent for each 1,000 feet above sea level.
Contact your local Sears Service Center or gas utility for further
information.

AWARNING

The appliance and its gas connection must be leak tested
before placing the appliance in operation.

AWARNING

>

The appliance and its individual shutoff valve must be discon­

nected from the gas supply piping system during any pressure
testing of the gas system at test pressures in excess of

VI

pound per square inch (3.5kPa).

>

The appliance must be isolated from the gas supply piping sys­

tem by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test pres­
sures equal or less than 1/2 pound per square inch (3.5kPa).

__________________AWARNING___________

Use pipe joint compound or teflon tape marked
resistant to the action of petroleum [Propane (LP.)]

as being

SEDIMENT TRAP

A sediment Crap shall be installed as close to the inlet of the

water heater as practical at the time of water heater installation.
The sediment trap shall be either a tee fitting with a capped nip­
ple in the bottom oudei or other device recognized as an effec­

tive sediment trap. If a tee fitting is used, it shall be installed in
conformance with one of the methods of installation shown
below.

Connecting the gas piping to the gas control valve of the water
heater can be accomplished by either of the two methods shown.

GAS PIPING WITH

FLEXIBLE CONNECTOR

I CAS SUPPLY PIPING

MANUAL
SHUTOFF

VALVE

FLEXIBLE CAS CONNECTOR

LABELED AS COMPLYING

CAS

CONTROL

VALVE

GAS PIPING WITH ALL BLACK IRON

PIPE TO GAS CONTROL

GAS SUPPLY PIPING

MANUAL

SHUTOFF

VALVE

CAS

CONTROL

VALVE

19

AWARNING

Contaminants in the gas lines may cause improper operation
of the gas control vaWe that may result in fire or explosion.
Before attaching the gas line be sure that all gas pipe is clean
on the inside. To trap any dirt or foreign material in the gas
supply line, a drip leg (sometimes called a sediment trap)
must be incorporated in the piping. The drip leg must be
readily accessible. Instsdl in accordance with the “Gas Pi|Mn^’
section. Refer to the latest edition of the National Fuel Gas

Code, ANSI Z223.1, also referred to as NFIV^ 54.