Section

2

— O peration

Guardian Air-cooled 6 kW, 8 kW and 10 kW Generators

OPERATION

pit

D. utility Voltage Pickup Sensor

• This sensor monitors utility power supply volt­

age. When that voltage is restored above 80 per­

cent of the nominal source voltage, a retransfer

time delay starts timing.

E. Retransfer Time Delay

• This timer runs for about 15 seconds.

• At end of a 15-second delay, circuit board

action de-energizes transfer relay in the trans­

fer switch.

• Retransfer to utility power source then occurs.

F. Engine Cool-down Timer

• When the load is transferred back to utility

power source, the engine cool-down timer

starts timing.

• The timer will run for about one minute, and

the generator will then shut down.

2.4 MANUAL TRANSFER OPERATION

♦ 2.4.1 TRANSFER TO GENERATOR

_______POWER SOURCE________________

To start the generator and activate the transfer

switch manually, proceed as follows;

1. Set the generator’s Auto/Off/Manual switch

to OFF.

Set the generator’s main circuit breaker to its

OFF (or open) position.

Turn OFF the utility power supply to the trans­

fer switch using the means provided (such as a

utility main line circuit breaker).

2

.

3.

A

DANGER

Do not attempt to activate the transfer

switch

manually until all power voltage supplies to

the switch have been positively turned

off.

Failure to turn off all power voltage supplies
may result in extremely hazardous and possibly

fatal electrical shock.

Figure 2.2

-

Manual Transfer Switch Operation

\

IDAI CfilMECTEI TO imUTY PONEH SOURCE

LOU COMECTEl TO STMS8Y HmU SOMCI

4. Use the manual transfer handle inside the

transfer switch to move the main contacts to

their "Standby” position, i.e., loads connected to

the standby power source (Figure 2.2).

5. Turn ON the utility power supply to the trans­

fer switch using the means provided (such as a

utility main line circuit breaker).

6. To crank and start the engine, set the

Auto/Off/Manual switch to MANUAL.

7. Let the engine stabilize and warm up for a few

minutes.

8. Set the generator’s main circuit breaker to its

ON (or closed) position. The standby power

source now powers the loads.

2A2

TRANSFER BACK TO UTILITY POWER SOURCE

When utility power has been restored, you will want

to transfer back to that source and shut down the

generator. This can be accomplished as follows:

1. Set the generator’s main circuit breaker to its

OFF (or open) position.

2. Let the engine run for a minute or two at no-

load to stabilize the internal temperatures.

3. Set the generator’s Auto/Off/Manual switch to

its OFF (or open) position. The engine should

shut down.

4. Chepk that utility power supply to the transfer

switch is turned OFF.

A

5.

DANGER

Do not attempt to activate the transfer switch
manually until all power voltage supplies

to the switch have been positively turned off.

Failure to turn off all power voltage supplies
may result in extremely hazardous and possibly

fatal electrical shock.

Use the manual transfer handle inside the

transfer switch to move the main contacts back

to their “Utility” position, i.e., loads connected

to the utility power source (Figure 2.2).

Turn ON the utility power supply to the trans­

fer switch using the means provided.

Set the system to automatic operation as out­

lined in “Automatic Transfer Operation,” section

2

.

2

.

2.5 SETTING THE EXERCISE TIMER

Your generator is equipped with an exercise timer.

Once it is set, the generator will start and exercise

once every 14 days, on the day of the week and at

the time of day you complete the following

sequence. During this exercise period, the unit

runs for approximately seven minutes and then

shuts down. Transfer of loads to the generator out­

put does not occur during the exercise cycle.