Section 3 — M aintenance

Guardian Air-cooled 6 kW, 8 kW and 10 kW Generators

MAINTENANCE

3=^

3.12 SERVICE SCHEDULE

ATTENTION: It is recommended

that

all service work

be performed by your nearest Generac/Guardian Authorized Dealer.

SYSTEM/COMPONENT

PROCEDURE

FREQUENCY

X = Action

R = Replace as Necessary

* = Notify Dealer

if Repair is Needed.

Inspect

Change

Clean

W = Weekly

M = Monthly

Y = Yearly

H = Hours

FUEL

Fuel lines and connections*

X

M

LUBRICATION

Oil level

X

M •

Oil

X

FIRST 9 H,

EVERY 100 H AND Y

Oil filter

X

FIRST 9 H,

EVERY 200 H AND Y

Oil line leakage*

X

100 H

COOLING

Enclosure louvers

X

X

W

EXHAUST LINE

Exhaust outlet

X

X

W

Spark arrestor*

X

Y

BATTERY

Remove corrosion,

ensure dryness

X

X

M

Clean and tighten

battery terminals

X

X

M

Check charge state

X

R

EVERY 6 M

Electrolyte level

(unsealed batteries only)*

X

R

EVERY 6 M

ENGINE AND MOUNTING

Air cleaner

X

R

100 H AND Y

6 kW foam

precleaner

X

EVERY 25 H OR

EVERY 3 M

Spark plug(s)

X

R

100 H AND Y

GENERAL CONDITION

Vibration, Noise, Leakage,

Temperature*

X

M

COMPLETE TUNE-UP*

TO BE COMPLETED BY A GENERAC/

GUARDIAN AUTHORIZED DEALER

Y