GENERAL

INFORMATION

Section 1 — G eneral Inform ation

Guardian Air-cooled 6 kW, 8 kW and 10 kW Generators

DANGER

Only qualified electricians or contractors should

attempt such installations, which must comply strictly
with applicable codes, standards and regulations.

1.1

UNPACKING/INSPEaiON

After unpacking, carefully inspect the contents

for damage.

® This standby generator set has been factory sup­

plied with a weather protective enclosure that is

intended for outdoor installation only.

* This standby generator set is packaged with an

automatic transfer switch.

® This UL listed, two-pole switch is rated at 100 AC

amperes at 250 volts maximum. This transfer

switch is for indoor use only.

------

M.

WARNING ik----------

A

If this generator is used to power electrical load

circuits normally powered by a utility power
source, you are required by code to install a trans­
fer switch. The transfer switch must effectively iso­

late the electrical system from the utility distribu­

tion system when the generator is operating (NEC
701). Failure to isolate an electrical system by such

means will result in damage to the generator and
also may result in injury or death to utility power

workers due to backfeed of electrical energy.

If any loss or damage is noted at time of delivery,

have the person(s) making the delivery note all

damage on the freight bill or affix his or her signa­

ture under the consignor's memo of loss or damage.

If you note loss or damage after delivery, separate

the damaged materials and contact the carrier for

claim procedures.

“Concealed damage” is understood to mean damage

to the contents of a package that is not in evidence

at the time of delivery, but is discovered later.

1.2

PROTECTION SYSTEMS

Unlike an automobile engine, the generator may have

to run for long periods of time with no operator pres­

ent to monitor engine conditions. For that reason, the

engine is equipped with the following systems that

protect it against potentially damaging conditions:

1. Low Oil Pressure Sensor 3. Overcrank

2. High Temperature Sensor 4. Overspeed

There are LED readouts on the control panel to

notify you that one of these faults has occurred.

There is also a “System Set” LED that is lit when all

of the following conditions are true:

1. The Auto/Off/Manual switch is set to the AUTO

position.

2. The “Not In Auto” dip switch is set to the OFF

position on the control board.

4 G e n e r a c * P o w e r S y e t e m s , I n c .

3. No alarms are present.

1.3

ADDITIONAL GENERATOR

FEATURES

Your generator offers additional features that are

not factory preset:

1. Remote Start ~ This allows you to remotely start

your generator with the Auto/Off Manual

switch set to AUTO.

2. Remote/Common Alarm - This allows for an

alarm, Ught, hom, etc., to activate when any fault

has occurred.

3. Remote Not Auto - The generator will not auto­

matically start during a utility failure.

These options may be set up by your nearest

Generac / Guardian Authorized Dealer.

1.4

FUEL REQUIREMENTS

AND RECOMMENDATIONS

With LP gas, use only the vapor withdrawal

system. This type of system uses the vapors

formed above the liquid fuel in the storage tank.

The engine has been fitted with a fuel carburetion

system that meets the specifications of the 1997

California Air Resources Board for tamper-proof

dual fuel systems. The unit will run on natural gas

or LP gas, but it has been factory set to run on nat­

ural gas. Should the primary fuel need to be

changed to LP gas, the fuel system needs to be

reconfigured. See section 1.8 (page 6) for instruc­

tions on reconfiguration of the fuel system.

Recommended fuels should have a Btu content of

at least 1,000 Btus per cubic foot for natural gas;

or at least 2,520 Btus per cubic foot for LP gas. Ask

your fuel supplier for the Btu content of your fuel.

Fuel pressure for both natural gas and liquid

propane set ups should be 11 inches to 14 inches

of water column (0.6 psi) at all load ranges.

1.5

FUEL CONSUMPTION

Model #

Nat. Gas (*)

LP Vapor (**)

1/2 Load Full Load

1/2 Load

Full Load

04077

(6

kw)

74.1

105.3

0.86/31.30

1.08/39.30

04109 (8 kw)

79.7

140.0

1.07/38.94

1.56/56.77

04079

(10 kw)

100.8

177.9

1.16/42.21

2.15/78.24

*Natural gas is in cubic feet per hour.

**LP is in gallons per hour/cubic feet per hour.

WARNING

Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even the
slightest spark can ignite such fuels and cause
an explosion. No leakage of fuel is permitted.
Natural gas, which is lighter than air, tends to
collect in high areas. LP gas is heavier than air
and tends to settle in low areas.