OPERATION

(J)

0

:

Section 2 — O peration

Guardian Air-cooled 6 kW, 8 kW and 10 kW Generators

A switch on the control panel (see Figure 3.1) allows

you to select the day and time for system exercise.

To select the desired day and time of day, proceed

as follows:

1. Verify that the Auto/Off/Manual switch is set

to AUTO.

2. Hold down the set timer switch until the gener­

ator starts (approximately 10 seconds) and

then release.

3. The generator will start and run for approxi­

mately seven minutes and then shut down on

its own. The exerciser will then be set to run at

that time of day every week.

NOTE;

The exerciser will only work in the AUTO mode

and will not work unless this procedure

is performed. The exerciser will need to be reset

every time the 12-volt battery is disconnected

and then reconnected. The exerciser WILL NOT

work if dip switch 2 (Remote Not Auto) is ON.

2.6

PROTECTION SYSTEMS

♦ 2.6.1 LOW OIL PRESSURE SWITCH________

This switch (Figure 2.3) has normally closed contacts

that are held open by engine oil pressure during

cranking and operating. Should oil pressure drop

below the 8 psi range, switch contacts close, and the

engine shuts down. The unit should not be restarted

until oil is added, and the Auto/Off/Manual switch

must be turned to OFF and then back to AUTO.

♦ 2.6.3 OVERCRANK

This feature prevents the generator from damaging

Itself when it continually attempts to start and

another problem, such as no fuel supply, prevents

it from starting. The unit will crank and rest for a

preset time limit. Then, it will stop cranking, and

the LED will light indicating an overcrank failure.

The Auto/Off/Manual switch will need to be set to

OFF and then back to AUTO to reset the generator

control board.

NOTE:

If the fault is not repaired, the overcrank fea­

ture will continue to activate.

2.6.3.1 Approximate Crank Cycle Times

• 15 seconds ON

• 15 seconds OFF

• 7 seconds ON

• 7 seconds OFF

• Repeat for 45 seconds

Approximately 90 seconds total

• 2.6.4 OVERSPEED_____ _____________ _

This feature protects the generator from damage by

shutting it down if it happens to run faster than the

preset kmlt. This protection also prevents the gener­

ator from supplying an output that could potentially

damage appliances connected to the generator cir­

cuit. Contact your nearest Generac/Guardian

Authorized Dealer if this failure occurs.

♦ 2.6.2 HIGH TEMPERATURE SWITCH_______

This switch’s (Figure 2.3) contacts close if the tem­

perature should exceed approximately 140° C (284°

F), initiating an engine shutdown. Your generator

will automatically restart and the LED will reset

once the temperature has returned to a safe oper­

ating level.

Figure

2.3

-

Low Oil Pressure and

High Temperature Switches

HIGH