background image

INSTALLATION

Section 6 - Installation

PRIMEPACT 66G and 66LP Recreational Vehicle Generators

From the junction box, route power supply wires

through approved conduit to either (a) double-pole,
double-throw transfer switch, or (b) approved isola­
tion receptacle. Connecting to a transfer switch or
isolation

receptacle

must

prevent

vehicle

electrical

circuits from being connected to two different power
supplies at the same time (such as generator and
dockside power).

• Conductors must be rated 221° F (105° C) or must be

of a larger conductor size.

6.7.5 GENERATOR AC CONNEQIONS

Generator AC output leads T1 (red), T2 (white) and T3
(black) come out of the generator as shown in
Figure 6.17. Leads T1 (red) and T3 (black) are “hot,”
while T2 (white) is the grounded neutral lead. There is
also a green lead that connects to ground in the junction
box of the recreational vehicle.

Figure 6.17 - Generator AC

Output

Leads

♦ 6.7.4 CONDUIT

A

3S

------

M.

CAUTION

M.

-----------

Do NOT connect electrical loads in excess of any

circuit breaker rating or you will develop prob­
lems with circuit breaker tripping, which causes a

loss of AC output. Also, do NOT exceed the gener­
ator's rated wattage capacity. Add the watts or

amperes of all lighting, appliance, tool and motor
loads the generator will operate at one time. This

total should be less than the unit's rated

wattage/amperage capacity.

Generac* Power Systems, Inc.

Route the connections between the generator and the

junction box through approved, flexible conduit. The

following general rules apply:

• Cut wiring to the required length and allow extra wire

for junction box connections.

Carefully prepare conduit ends to prevent sharp

edges from cutting through wiring insulation.

• Route conduit so it does not interfere with generator

movement.

• If you use metallic conduit, vapor seal the end of the

conduit where it enters the junction box. Do this
because flexible metallic conduit is not vaporproof
along its entire length.

6.7.5 ISOLATING DIFFERENT POWER SOURCES

Connections from the junction box must terminate in a
double-pole, double-throw transfer switch (Figure 6.18,
Page 3.3), An alternate method for isolating different

power

sources

is

by

using

an

Isolating

receptacle

(Figure 6.19, Page 33). Whichever method you use, you

must be certain that both power sources are NOT con­
nected at the same time.

♦ 6.7.6 POWER SUPPLY CORD

Line T1 (red) to T2 (white) is protected against overload
by a 30-amp circuit breaker (CBl). Use this line-to-neu-
tral connection separately to operate 120-volt, single-
phase, 60 Hertz, AC loads requiring up to 3,300 watts
of

power

for

PrimePact

66G

or

3,100

watts

for

PrimePact 66LP Line T3 (black) to T2 (white) also is
protected against overload by a 30-amp circuit breaker

(CB2). Use this line-to-neutral connection separately to

operate similar loads. However, be sure the total unit
load does not exceed the maximum rating of the gener­
ator. The neutral line (T2, white) on all units is a

grounded neutral.

The power supply cord must comply with all applicable
codes,

standards

and

regulations.

It

must

be

large

enough to handle the full amperage to which it will be
subjected. (See page 33 for illustration.)

6.7.7 GROUND FAULT CIRCUIT INTERRUPTERS

The National Electrical Code (NFPA 70, 551-7) requires
that you install ground fault circuit interrupters (GFCIs)
on all external and some internal electrical receptacles.
Contact your manufacturer or dealer for recommenda­
tions.

6.8

BATTERY INSTALLATION

6.8.1 RECOMMENDED BATTERY __________________

Install a battery that meets the following requirements:

The battery must be a 12-volt, automotive type

storage battery.

• For prevailing ambient temperatures above 32° F (0°

C), use a battery rated 70 amp-hours and capable of
delivering 400 cold-cranking amperes.

For prevailing ambient temperatures below 32° F (0°

C), use a battery rated 95 amp-hours and capable of
delivering 400 cold-cranking amperes.

NOTE:

If the battery is to be used to power other vehicle
accessories, as well as start the generator, you may
need a battery with a larger capacity.