25

either a 0% or a 100% duty cycle. The duty cycle is programmed as the high-time count of
1024 total counts of the Rabbit 2000’s timer B. Thus, 256 counts would be 25% of 1024
counts, and corresponds to a 25% duty cycle.

Table 2 lists typical DA1 voltages measured for various duty cycle values with a load
larger than 1 M

Ω.

It is important to remember that the DA1 output voltage will not be realized instanta-
neously after programming in a value. There is a settling time because of the RC time con-
stant (R24 × C22), which is 10 ms. For example, the voltage at any given time is

V = V

P

– (V

P

– V

DA1

)e

(-t/RC)

(EQ 1)

where V is the voltage at time t, V

P

is the programmed voltage, V

DA1

is the last DA1 out-

put voltage from the D/A converter, and RC is the time constant (10 ms). The settling will
be within 99.326% (or within about 21 mV for a 3 V change in voltage) after five time
constants, or 50 ms. Six time constants, 60 ms, will allow settling to within 99.75% (or to
within about 8 mV for a 3 V change in voltage). Seven time constants, 70 ms, will allow
settling to within 99.91% (or to within about 3 mV for a 3 V change in voltage).

An LM324 op amp, which can comfortably source 10 mA throughout the D/A converter
range, drives the D/A converter output. If the output voltage is above 1 V, the D/A con-
verter can comfortably sink 10 mA. Below 1 V, the D/A converter can only sink a maxi-
mum of 100 µA.

To summarize, DA1 is provided uncalibrated, can be programmed with a resolution of
5 mV and a peak-to-peak ripple less than 20 mV over the range from 0.7 V to 3.5 V and
0 V. The settling time to within 21 mV is 50 ms.

Table 2. Typical DA1 Voltages for Various Duty Cycles

Duty Cycle

(%)

Voltage

(V)

Programmed Count

0

0.002

0–122

12

0.620

123

25

1.242

256

50

2.483

512

72

3.567

742

100

3.567

743–1024