pRESSURE TESTING GAS SUppLY
pIpING SYSTEM
Test pressures In Excess Of 1/2 pSIG
(3.5 kPa)

1. Disconnect fireplace and its individual equip-

ment shutoff valve from gas supply piping

system. Pressures in excess of 1/2 psig (3.5 kPa)

will damage fireplace gas regulator.

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas fireplace or opening main gas

valve located on or near gas meter for natural

gas fireplace, or using compressed air.

4. Check all joints of gas supply piping system.

Apply noncorrosive leak detection fluid to all

joints. Bubbles forming show a leak. Correct

all leaks at once.

5. Reconnect fireplace and equipment shutoff

valve to gas supply. Check reconnected fittings

for leaks.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)

1. Close equipment shutoff valve (see Figure 34).

2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas fireplace or opening main gas

valve located on or near gas meter for natural

gas fireplace, or using compressed air.

3. Check all joints from propane/LP supply tank

or gas meter to equipment shutoff valve (see

Figure 35 for propane/LP or Figure 36 for

natural gas). Apply noncorrosive leak detec-

tion fluid to all joints. Bubbles forming show

a leak. Correct all leaks at once.

FIREPLACE

INSTALLATION

Continued

pRESSURE TESTING FIREpLACE GAS
CONNECTIONS

1. Open equipment shutoff valve (see Figure 34).

2. Open main gas valve located on or near gas

meter for natural gas or open supply tank

valve for propane/LP gas.

3. Make sure control knob of fireplace is in the

OFF position.

4. Check all joints from equipment shutoff valve

to thermostat gas valve (see Figure 35 or 36).

Apply noncorrosive leak detection fluid to all

joints. Bubbles forming show a leak. Correct

all leaks at once.

5. Light fireplace (see Operating Fireplace, page

28). Check all other internal joints for leaks.

6. Turn off fireplace (see To Turn Off Gas to

Appliance, page 29).

Open

Closed

Equipment
Shutoff Valve

Figure 34 - Equipment Shutoff Valve

Figure 36 - Checking Gas Joints for

Natural Gas Fireplace

Figure 35 - Checking Gas Joints for

Propane/LP Gas Fireplace

Propane/LP
Supply Tank

Gas Valve

Equipment
Shutoff Valve

Gas
Meter

Gas Valve

Equipment Shutoff Valve