Venting installation instructions, Continued – Desa (V)T32EN-A Series User Manual

Page 10

Advertising
background image

10

www.desatech.com

116647-01A

Vertical (V)

Required

Vertical (V) Vertical Pipe Horizontal (H)
*43

3

/

4

" min.

None

30" max.

53

3

/

4

" min.

1 ft.

48" max.

65

3

/

4

" min.

2 ft.

60" max.

77

3

/

4

" min.

3 ft.

84" max.

89

3

/

4

" min.

4 ft.

20' max.

* Ground Floor Corner Venting

Figure 15 - Horizontal Termination Configuration for Corner

Installation Using One 90° Elbow

Square

Termination

Wall

Firestop

Not to Exceed

(H) Limits

As Required for (V)

See Chart for Pipe

Section Required

45°

Elbow

90° Elbow

90° Elbow

Square

Termination

Wall

Firestop

45° Elbow

Not to Exceed

(H) Limits

12" Minimum

CORNER INSTALLATION
Recommended Applications:
• Corner ground floor installation
• Ground floor installation where pipe vents horizontally through wall

(over 12" horizontal pipe)

• Basement installation where one foot clearance from ground to

termination is possible

Vertical (V) Horizontal (H)

29

3

/

4

"

17" max.

Horizontal High

Wind Square

Termination

Wall Firestop

45° Elbow

Figure 14 - Horizontal Termination Configuration for Square or

Round Termination

45° Elbow

Wall

Firestop

Horizontal

Round

Termination

Exterior Portion of

Wall Firestop (Round

Termination Only)

GROUND FLOOR INSTALLATION
Recommended Applications:
• Installation using cabinet surrounds
• Through the wall using round or

square termination

(up to 12" horizontal pipe)
• NOT FOR CORNER
INSTALLATION

VENTING INSTALLATION

INSTRUCTIONS

Continued

VENTING INSTALLATION INSTRUCTIONS

Installation Planning (Cont.)

Adjustable

Pipe 12" Max.

Horizontal Termination Configurations

Figures 14 through 18 show different configurations and alternatives

for venting with horizontal termination. Each figure includes a chart

with critical minimum and maximum dimensions which MUST be

met. IMPORTANT: Remember that a horizontal run of venting must

have a 1/4" rise for every 12" of run toward the termination.

WARNING: Never run vent downward as this may

cause excessive temperatures which could cause a

fire. Operation of improperly installed and maintained

venting system could result in serious injury, property

damage or loss of life.