Venting installation instructions, Continued – Desa (V)T32EN-A Series User Manual

Page 13

Advertising
background image

13

13

www.desatech.com

116647-01A

VENTING INSTALLATION

INSTRUCTIONS

Continued

Flat Ceiling Installation

1. Cut a 10

3

/

4

" square hole in the ceiling using the locating hole as

a center point. The opening should be framed to 10

3

/

4

"x10

3

/

4

"

(273 mm x 273 mm) inside dimensions, as shown in Figure 9 on

page 8 using framing lumber the same size as the ceiling joists.

If the area above the ceiling is an insulated ceiling or a room,

nail firestop from the top side. This prevents loose insulation

from falling into the required clearance space. Otherwise, install

firestop below the framed hole. The firestop should be installed

with no less than three nails per side (see Figure 20).

2. Assemble the desired lengths of pipe and elbows necessary to

reach from the fireplace flue up through the firestop. Be sure all

pipe and elbow connections are fully twist-locked (see Figure

8, page 8).

3. Cut a hole in the roof using the locating hole as a center point.

(Cover any exposed open vent pipes before cutting hole in roof.)

The 10

3

/

4

"x10

3

/

4

" hole must be measured on the horizontal;

actual length may be larger depending on the pitch of the roof.

There must be a 1" clearance from the vent pipe to combustible

materials. Frame the opening as shown in Figure 9, page 8.

4. Connect a section of pipe and extend up through the hole.

Note:

If an offset is needed to avoid obstructions, you must sup-

port the vent pipe every 3 feet. Use wall straps for this purpose

(see Figure 19, page 12). Whenever possible, use 45° elbows

instead of 90° elbows. The 45° elbow offers less restriction to

the flow of the flue gases and intake air.

5. Place the flashing over the pipe section(s) extending through the

roof. Secure the base of the flashing to the roof and framing with

roofing nails. Be sure roofing material overlaps the top edge

of the flashing as shown in Figure 19, page 12. There must be

a 1" clearance from the vent pipe to combustible materials.

6. Continue to add pipe sections until the height of the vent cap

meets the minimum building code requirements described in

Figure 7 on page 6. Note: You must increase vent height for

steep roof pitches. Nearby trees, adjoining rooflines, steep

pitched roofs and other similar factors may cause poor draft or

down-drafting in high winds. Increasing the vent height may

solve this problem.

Figure 20 - Installing Firestop

If area above is not a room, install

firestop below framed hole.

If area above is a room or

insulated area, install firestop

above framed hole.

7. Twist-lock the vent cap onto the last section of vent pipe.
Note:

If the vent pipe passes through any occupied areas above the

first floor, including storage spaces and closets, you must enclose

pipe. You may frame and sheetrock the enclosure with standard

construction material. Make sure and meet the minimum allow-

able clearances to combustibles. Do not fill any of the required air

spaces with insulation.

VENTING INSTALLATION INSTRUCTIONS

Installation for Vertical Termination (Cont.)

Vertical Termination Configurations

Figures 21 through 24 show four different configurations for verti-

cal termination.

Figure 21 - Vertical Venting Configuration Using Two 90°

Elbows with Two Horizontal Runs (Vertical Round High Wind

Termination Shown)

Venting with Two 90° Elbows

Vertical (V)

Horizontal (H

1

) +

Horizontal (H

2

)

5' min.

2' max.

6' min.

4' max.

7' min.

6' max.

8' min.

8' max.

20' max.

8' max.

Note: Install

restrictor into inner

collar of fireplace

as shown.

45° Elbow

Advertising
This manual is related to the following products: