CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections,

internal and external to unit, for leaks after installing

or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a

leak. Apply noncorrosive leak detection fluid to all joints.

Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1. Disconnect fireplace and its individual equipment shutoff valve

from gas supply piping system. Pressures in excess of 1/2 psig

(3.5 kPa) will damage fireplace gas regulator.

2. Cap off open end of gas pipe where equipment shutoff valve

was connected.

3. Pressurize supply piping system by either opening propane/LP

supply tank valve for propane/LP gas fireplace or opening main

gas valve located on or near gas meter for natural gas fireplace

or using compressed air.

FIREPLACE INSTALLATION

Continued

FIREPLACE INSTALLATION

Connecting Fireplace To Gas Supply

Checking Gas Connections

CONNECTING FIREPLACE TO GAS SUPPLY

Installation Items Needed

• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not provided)
1. Open lower louver door panel by gently pulling forward.
2. Route flexible gas line (provided by installer) from equipment

shutoff valve to fireplace. Route flexible gas supply line through

one of the access holes on side of fireplace.

3. Attach flexible gas line from gas supply to control valve (see

Figure 32).

4. Check all gas connections for leaks. See Checking Gas

Connections

.

Figure 32 - Connecting Flexible Gas Line to Electronic Valve

1/2" NPT Incoming

Gas Line

Inlet Pressure Tap

Outlet Pressure Tap

Equipment

Shutoff Valve

Flexible Gas Line

Do NOT Kink

Note: Wire Connections Not Shown for Clarity

Red Surface Indicates

For Propane/LP Use Only

Open

Closed

Equipment

Shutoff

Valve

Figure 33 - Equipment Shutoff Valve

4. Check all joints of gas supply piping system. Apply noncor-

rosive leak detection fluid to all joints. Bubbles forming show

a leak. Correct all leaks at once.

5. Reconnect fireplace and equipment shutoff valve to gas supply.

Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1. Close equipment shutoff valve (see Figure 33).
2. Pressurize supply piping system by either opening propane/LP

supply tank valve for propane/LP gas fireplace or opening main

gas valve located on or near gas meter for natural gas fireplace

or using compressed air.

3. Check all joints from propane/LP supply tank or gas meter to equip-

ment shutoff valve (see Figure 34 for propane/LP or Figure 35 for

natural gas). Apply noncorrosive leak detection fluid to all joints.

Bubbles forming show a leak. Correct all leaks at once.

Figure 34 - Checking Gas Joints for Propane/LP Gas Fireplace

Propane/LP

Supply Tank

Gas Valve

Equipment

Shutoff

Valve

Figure 35 - Checking Gas Joints for Natural Gas Fireplace

Gas

Meter

Gas Valve

Equipment

Shutoff

Valve