3.11 4mA Offset Calibration

@Description

Stores the current output value as 4 mA reference at the specified analog
output module.(only 6021)

@Syntax

$(Addr)0<CR>

$

Command leading code

(Addr)

Address ID

0

Command Code

@Response

!(Addr)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid or no synchronized sampling
command was issued.

(Addr)

Address ID.

@Example

User command:

$060<CR>

Response:

!06<CR>

To perform the 4 mA calibartion for analog output module at address 06H.

Note : Analog output module should be trimmed to the correct value by “Trim

Calibration” command before to execute “4 mA Calibration”. Refers
to Chapter 5 “Analog Output Calibration” for details.