ADLINK ND-6021 User Manual

Page 52

Advertising
background image

46

Command Set

@Response

!(Addr)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr)

Address ID

@Example

User command:

~0621123F0<CR>

Response:

!06<CR>

06

Address ID

2

Set host watchdog timer and safe state value.

1

Enable host watchdog timer.

12

Timeout value. 0x12 = 18
18 * 53.3 = 959 ms (Firmware Version 1.x)
18 * 100 = 1800 ms (Firmware Version 2.x)

3F0

0x3F0 is hexadecimal
Analog output value is 4.923 mA for 0-20mA
Analog output value is 4.923 mA for 4-20mA
Analog output value is 2.462 V for 0-10 V

Analog output safety value are as following :

For type is 0 ~20 mA or 4~20 mA (Output Range is 0x30, 0x31)

value = (0x3F0 / 0xFFF) * 20 mA = 4.923 mA

For type is 0 ~10V (Output Range is 0x32)

value = (0x3F0 / 0xFFF) * 10 V = 2.462 V

User command:

~062112800800800800<CR>

Response:

!06<CR>

Advertising