16 current readback – ADLINK ND-6021 User Manual
Page 46
Advertising
40
• Command Set
3.16 Current Readback
@Description
Read the estimated current output value at the specified analog output
module.
@Syntax
$(Addr)8<CR>
$
Command leading code. (1-character)
(Addr)
Address ID. (2-character)
6
Function code of last value readback.
(1-character)
@Response
!(Addr)(Data)<CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID.
(Data)
The current analog output value, the data format
depends on module configuration.
@Example
User command:
$088<CR>
Response:
!0802.000<CR>
This analog output module return the latest output value is 2.000 mA at
address 08H, if data format is engineering units and the signal range is
0~20mA.