Command Set

37

3.13 Trim Calibration

@Description

Trims the specified analog output module a specified number of units up or
down.

@Syntax

$(Addr)3(Counts)<CR>

$

Command leading code

(Addr)

Address ID

3

Function Code

(Counts)

Number of counts to increase or decrease the output
current.
Range 00 - 5F : 0 to +95 counts (increase)
Range A1 - FF : -95 to -1 counts (decrease)
1 count equals approximately 4.88

µA or 2.44mV

(4.88mV for ND-6024)

@Response

!(Addr)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr)

Address ID.

@Example

User command:

$06314<CR>

Response:

!06<CR>

Increase analog output value about 97.6

µA (14H * 4.88µA = 97.6µA) at

address 06H.

Note : Analog output module trim calibration should have a corrent calibration

wiring. Refers to Chapter 5 “Analog Output Calibration” for details.