2.2 Initializing a Brand-New Module
2.2.1 Objective of Initializing a Brand-New NuDAM
All NuDAM modules. except NuDAM-6520 and NuDAM-6510, in a RS-485 
network must have an unique address ID, however, every brand-new 
NuDAM has a factory default setting as following : 
♦
Address ID is 01.
♦
Baud rate is 9600 bps
♦ Check-sum
disable
♦
Host Watchdog timer is disable
Therefore, to configure the brand-new NuDAM before using is necessary, 
otherwise the address ID will be conflict with others modules because the ID 
of new modules are identity . The baud rate may also be changed according 
to user‘s requirements. 
The following sections show how to initialize a brand-new module, which is 
applicable for initializing NuDAM-6050, NuDAM-6052, NuDAM-6053, 
NuDAM-6054, NuDAM-6056, NuDAM-6058, NuDAM-6060, and 
NuDAM-6063.