11 digital output (continued) – ADLINK ND-6053 User Manual
Page 83
 
Command Set
• 75
3.11 Digital Output (Continued)
( 6056, 6058 )
@Description
Set direct digital output channel value at specified address. This command 
is only available to modules involving the multiport digital output function. 
@Syntax
#(Addr)(Port)(ChNo)(OutData)<CR> (6056,6058 only)
#
Command leading code. (1-character)
(Addr)
Address ID (2-character)
(Port)
Set direct channel value to indivisual port 
H: for 6056 channel 14 to 8 
L: for 6056 channel 7 to 0 
A: for 6058 port A 
B: for 6058 port B 
C: for 6058 port C (1-character) 
(ChNo)
Channel value 7 ~ 0
(OutData)
1: ON 
0: OFF 
(1-character) 
 * if the port of ND-6058 is in input mode, output data to this port will be 
ignore. 
@Response
<CR>
or
?(Addr)<CR>
>
Command is valid
?
Command is invalid.
(Addr) Address
ID.