• Initializtion & Installation
2.2.2 Default
State
The NuDAM I/O modules must be set at Default State when you want to 
change the default settings, such as the ID address, baud rate, check-sum 
status etc. All NuDAM I/O modules have an special pin labeled as 
DEFAULT*. The module will be in Default State if the DEFAULT* pin is 
shorted to ground when power ON. Under this state, the default 
configuration is set as following : 
♦
Address ID is 00
♦
Baud rate is 9600 bps
♦ Check-sum
disable
Therefore, the communication between host and the module will can be 
easily set as the same configuration, the initialization of a module will be 
possible no matter what configuration is set under operating state. 
For ND-6053, ND-6054 and ND-6056, the pin 6 is used for both DI15(DO15) 
and DEFAULT*, and also the ND-6063, the pin 6 is used for both RL8 COM 
and DEFAULT*. The jumper setting is as below, and the default setting is 
DI15(D015) or RL8 COM. When you want to use ND-6053, ND-6054, 
ND-6056 or ND-6063 as Default*, you should open the module case to set 
the JP2. 
JP2
1 2 3
JP2
1 2 3
DI15 
(DO15) 
INIT*
DI15 
(DO15) 
INIT*
INIT*
DI15, DO15, RL8 COM