ADLINK ND-6053 User Manual
Page 87
 
Command Set
• 79
(Status)
0 : Data has been sent at least once before. 
1 : Data has been sent for the first time since a 
synchronized sampling command was 
issued.(1-character) 
(IOFlag)
Status of programmable I/O 
0x00: A(O/P) B(O/P) CH(O/P) CL(O/P) 
0x01: A(O/P) B(O/P) CH(O/P) CL(I/P) 
0x02: A(O/P) B(O/P) CH(I/P) CL(O/P) 
0x03: A(O/P) B(O/P) CH(I/P) CL(I/P) 
0x04: A(O/P) B(I/P) CH(O/P) CL(O/P) 
0x05: A(O/P) B(I/P) CH(O/P) CL(I/P) 
0x06: A(O/P) B(I/P) CH(I/P) CL(O/P) 
0x07: A(O/P) B(I/P) CH(I/P) CL(I/P) 
0x08: A(I/P) B(O/P) CH(O/P) CL(O/P) 
0x09: A(I/P) B(O/P) CH(O/P) CL(I/P) 
0x0A: A(I/P) B(O/P) CH(I/P) CL(O/P) 
0x0B: A(I/P) B(O/P) CH(I/P) CL(I/P) 
0x0C: A(I/P) B(I/P) CH(O/P) CL(O/P) 
0x0D: A(I/P) B(I/P) CH(O/P) CL(I/P) 
0x0E: A(I/P) B(I/P) CH(I/P) CL(O/P) 
0x0F: A(I/P) B(I/P) CH(I/P) CL(I/P) 
*I/P input mode, O/P output mode. 
(DataOut)
Value of digital output channel. (2-character)
(DataIn)
Value of digital input channel. (2-character)
(DIn)
Value of dedicated digital input channel 3-0 for 
ND-6058. The first character is 0 (2-character) 
(DataInH)
Value of digital input channel 15-8 (2-character)
(DataInL)
Value of digital input channel 7-0 (2-character)
(DataInA)
Value of port A channel 7-0 (2-character)
(DataInB)
Value of port B channel 7-0 (2-character)
(DataInC)
Value of port C channel 7-0 (2-character)