Programming: There are four parameters to program. Each is programmed in the same

sequence. The control panel has four pushbuttons labeled SELECT MENU, Cursor UP,

Cursor DOWN and SAVE. The associated Power Supply is provided with an IEC AC power

cord and On / Off switch.

LED Display: The LED display provides two rows of text. When the system is powered

up, the LED display will read “Display Devices” and “Current Temp (number).” The two-
digit number indicates the current temperature. Pressing the SELECT MENU button will

provide access to different programmable functions. If buttons are not pressed, the

display will automatically reset to “Current Temp” display after approximately 30 seconds.

Programming Temperature Control Level One: Press the SELECT MENU button once

and the display will read “Set Fan Lev1 (number)”. This number indicates the

temperature at which the Control One fans will begin operation. The second row of text

will change between “Current Temp” and current system status. If current temp is higher

than programmed point for level 1 fans, the display will indicate “Fans On Level 1”. Press

the UP or DOWN button to select desired temperature for Control One fans. Press SAVE.

Programming Temperature Control Level Two: Press the SELECT MENU button to

display “Set Fan Lev2 (number)”. This number indicates the temperature at which the

Control Two fans will begin operation. Press the UP or DOWN button to select desired

temperature for Control Two fans. Press SAVE.

Programming Alarm Level: Press the SELECT MENU button to display “Set Alarm Lev.

(number)”. This number indicates the temperature at which the audible alarm will sound.

Press the UP or DOWN button to select desired temperature for Audible Alarm. Press

SAVE.

Programming Power Off: Pressing the SELECT MENU button again will show “Set

Power Lv”. This will provide removal of power from the switched AC outlet. Press the UP

or DOWN button to select desired temperature for removal of power at switched AC.

Press SAVE.

Selecting Temp. Standard: Pressing the SELECT MENU button again will show either

Fahrenheit or Celsius. Pressing the Up or Down button will change the temperature
format. Press SAVE.