Temperature controller optional rs232 interface – Display Devices SE-B6-10 Soffit Series User Manual

Page 7

Advertising
background image

01-07

7

tel: 303.412.0399

www.displaydevices.com

fax: 303.412.9346

[email protected]

5880 Sheridan Blvd., Arvada, Colorado 80003

Temperature Controller

OPTIONAL RS232 Interface

Hardware

Standard three pin hookup, 2,3,5, on DB9.

Baud rate 9600,N,8,1.

No handshaking.

Software

ASCII letters followed by a delimiter and carriage return (ASCII 13).


Commands from Host to Controller:

Command

Description

Example

Q

Request Current Temperature

Q

Axxx

Set Fan Level 1

A078

Bxxx

Set Fan Level 2

B083

Cxxx

Set Alarm Level

C090

Dxxx

Set Power Cutoff Level

D100

xxx-temperature Carriage Return (13)

Communications from Controller to Host:

Command

Description

Example

T xxx

Current Temperature

T 073

G

Fan Level 1 On

G

H

Fan Level 2 On

H

I

Alarm On

I

J

Power has been switched off

J

S (O,C)

Door Switch is Open/Closed

SO SC

M

Motion Sensor Tripped

M

K

Received Set command, Executed OK

K

X

Can not understand Command

X

xxx-temperature

Carriage Return (13)

Notes:

All temperatures are in Fahrenheit.

Host program to convert to Celsius if required.
G,H,I,J are sent every few seconds when those levels have been tripped.

S is sent upon change of state.

M is sent upon shock sensor being tripped.

Temperature set range is from 1 to 190°, Fahrenheit.

Return temperature has a space after the „T‟ if positive, a – if negative.

Return temperature range is –140° to +190°.