Figure 22 – DuraVent DuraTech 5-8 User Manual

Page 15

Advertising
background image

15

Figure 21

Figure 23

to install the remainder of the Combustion Air

System. The Support Box must remain level,

and the top edge of the box must cover the

edge of the roof’s decking material. Mobile

home chimney installations are roof supported.

Do not seal openings in flashing.

A1. Place Appliance, Frame Opening:

Follow Step 1 and 2 from “Ceiling-Supported”

method detailed earlier. Refer to Table 1 for

clearance and framing specifications. If it is

desired to install through a cathedral ceiling

(Fig.20), then the hole is cut in the roof. If a

separate ceiling and roof exists, as shown in

Fig.19 (Low Attic), first cut and frame a ceiling

opening as in “Ceiling-Supported” Step 2.

A2. Install Support Box: Slip the Square

Support Box, Reduced Clearance Support

Box, or the CAS Ceiling Support into the

framed opening so the square portion projects

at least 2” below the finished ceiling and rafters

(bottom of round portion is 5” below, Fig.7),

and extends above the ceiling to framing or

decking materials to which it can be nailed.

Level the Support Box, and slit the corners to

the roofline where they extend beyond it. Bend

the flaps (created by the slitting) flush with the

roof, and nail the Support Box to the roof or

ROOF SUPPORT

TRIM COLLAR

FINISHING COLLAR

DURABLACK

SLIP CONNECTOR

USE 4 NAILS (OR

SCREWS) ON

EACH SIDE OF

SUPPORT

ROOF SUPPORT

(SUPPORT

BRACKETS AND

BAND)

SECURE ROOF

SUPPORT BAND TO

CHIMNEY USING

4 SHEET METAL

SCREWS

TIGHTEN BOLT

ON ROOF

SUPPORT BAND.

Figure 22

FLOORING

DURATECH CHIMNEY

PIPE

ROOF SUPPORT

MIN OF 3” BELOW

CEILING OR

EXPOSED FRAMING

FIRESTOP

RADIATION SHIELD

(TRIM RADIATION

SHIELD IF NEEDED

TO AVOID ROOF

SUPPORT)

FRAMING

MEMBERS

(ALL SIDES)