5chimney height, Chimney placement, Chimney enclosure require- ments – DuraVent DuraTech 5-8 User Manual

Page 5

Advertising
background image

ATTIC

INSULATION

SHIELD

FIRESTOP

RADIATION

SHIELD

(INSIDE)

ENCLOSURE

MUST HAVE 2

INCHES OF

CLEARANCE

BETWEEN

CHIMNEY AND

WALL

FIRST

FLOOR

OCCUPIED

SECOND

FLOOR

ATTIC /

UNOCCUPIED

SPACE

5

CHIMNEY HEIGHT

The National Fire Protection Association

Standard #211 states: “Chimneys shall extend

at least three feet above the highest point

where it passes through the roof of a building,

and at least two feet higher than any portion

of a building within ten feet.” (Fig.1) DuraTech

Chimney may be installed up to 60 feet high. If

the chimney extends more than 5 feet above

the roof, an Extended Roof Bracket must be

used (see page 12). Due to the overlap of the

joints, subtract 1-1/4 inches from each Chimney

Section’s height to calculate installed height.

CHIMNEY PLACEMENT

When deciding the location of your chimney,

try to avoid modifications to roof beams and

other structural components of the building.

CHIMNEY ENCLOSURE REQUIRE-

MENTS

Through Rooms: Interior chimneys shall be

enclosed where they extend through closets,

storage areas, occupied spaces, or anyplace

where the surface of the chimney could be

contacted by persons or combustible materials.

Maintain at least a 2-inch air space between

the outer wall of the chimney and the enclosure

(Fig.2).

Multi-Story: Consult local building codes for

requirements in your area. In the U.S., the

National Fire Protection Association Standard

#211 states: “Factory-built chimneys that

pass through floors of buildings requiring the

protection of vertical openings shall be enclosed

with approved walls having a fire resistance

rating of not less than one hour when such

chimneys are located in a building less than

4 stories in height, and not less than 2 hours

when such chimneys are located in a building

more than 4 stories in height.” In Canada,

Figure 1

Figure 2

2 FT MIN ABOVE HIGHEST

POINT OF ROOF WITHIN

10 FT

10 FT

3 FT MIN

ABOVE

ROOF

except in single-family and two-family dwellings,

chimneys which extend through another story

must have an enclosure with a fire resistance

rating equal to or greater than that of the floor or

SUPPORT

BOX