115 vac, This gate operator must be properly grounded, Danger – DoorKing 6100 User Manual

Page 18

Advertising
background image

6050-065-L-11-08

16

High Voltage
Conduit

Neutral

115 V

A

C

Chassis

Ground

115 VAC

2.1 High Voltage Wire Runs

2.2 High Voltage Terminal Connection

The distance shown in the chart is measured in “Feet” from the operator to the power source. If power wiring is greater
than the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a
separate junction box must be installed for the operator connection. The wire table is based on stranded copper wire. Wire
run calculations are based on a 110 VAC power source with a 3% voltage drop on the power line, plus an additional 10%
reduction in distance to allow for other losses in the system.

This table illustrates the high voltage wire size and distance requirements.

Model Type

Amps Required

Wire Size / Distance in Feet

12 AWG

10 AWG

8 AWG

6 AWG

4.3

215

345

575

890

6050 Single

8.6

105

170

285

430

6050 Dual

5.4

170

275

460

685

6100 Single

10.8

85

135

230

340

6100 Dual

DANGER

HIGH VOLTAGE!

SECTION 2 - WIRING

Before attempting to connect any wiring to the operator, be sure that the circuit breaker in the electrical panel is in the OFF
position. Permanent wiring must be installed to the operator as required by local electrical codes. It is recommended that a
licensed electrical contractor perform this work.
Since building codes vary from city to city, we highly recommend that you check with your local building department prior
to installing any permanent wiring to be sure that all wiring to the operator (both high and low voltage) complies with local
code requirements.

THIS GATE OPERATOR MUST BE PROPERLY GROUNDED!!

Section 1 MUST be completed before power can be turned on.

Route incoming high voltage power through conduit and into the operator

as shown.

Be sure wiring is installed in accordance with local codes. Be sure to color

code all wiring.

It is recommended that a surge suppressor be installed on the high voltage

power lines to help protect the operator and circuit board from surges and
power fluctuations.

Secondary operator in a dual operator application gets power through the

8-wire connector that links the 2 operators together. See 2.8
Primary/Secondary (dual) gate connection.