3 main terminal description – DoorKing 6100 User Manual

Page 19

Advertising
background image

6050-065-L-11-08

17

2.3 Main Terminal Description

lf SW 1, switch 3 is ON,

this input is identical to
Single Button Activation.

lf SW 1, switch 3 is OFF,

this terminal becomes the
logic output of the loop
detector that is plugged into
the open (Exit) loop port.

1

ON

2

3

4

5

6

7

8

SW 1

When gate is closed, input will open gate.

When gate is open and auto close

timer SW 1, switch 4 is turned on,
input will re-set and hold timer.

When gate is open and auto close

timer SW 1, switch 4 is turned off,
input will close gate.

When gate is closing, input will

reverse gate.

1

ON

2

3

4

5

6

7

8

SW 1

When gate is closed, this input has no

affect on the gate operator.

When gate is open and auto close

timer SW 1, switch 4 is turned ON,
input will re-set and hold timer.

When gate is open and auto close

timer SW 1, switch 4 is turned OFF,
input will prevent gate from closing.

When gate is closing, input will

reverse gate if SW 1, switch 5 is OFF.

When gate is closing, input has no

affect on the gate operator if SW 1,
switch 5 is ON (set for shadow input).

1

ON

2

3

4

5

6

7

8

1

ON

2

3

4

5

6

7

8

SW 1

SW 1

Operation of relay is dependent on

setting of SW 1, switches 1 and 2.
Relay contacts can be set for
Normally Open (NO) or Normally
Closed (NC) operation.

Contact

rating is 1 amp maximum at
24-volts DC.

1

ON

2

3

4

5

6

7

8

NC

NO

SW 1

24-volt DC magnetic lock power

is provided constantly except when
the gate is opening or open.

18

16

15

12

11

LOW VOLTAGE COMMON

LOW VOLTAGE COMMON

MAGNETIC LOCK OUTPUT

DRY RELAY CONTACT

DRY RELAY CONTACT

CLOSE INPUT

(Use DoorKing 3-Button station ONLY)

OPEN INPUT

(Use DoorKing 3-Button station ONLY)

REVERSE (SAFETY) INPUT/

SHADOW INPUT

SINGLE BUTTON ACTIVATION INPUT 2/

OPEN LOOP LOGIC OUTPUT

SINGLE BUTTON ACTIVATION INPUT 1

24 VAC Radio Receiver Power Only

(250 ma. maximum)

12 VAC Magnetic Counter Power Only

(150 ma. maximum)

PULSE 1

Input from Primary Operator

PULSE 2

Input from Secondary Operator

NOT USED

115 VAC MOTOR (CLOSE)

115 VAC MOTOR (OPEN)

115 VAC POWER INPUT

115 VAC POWER NEUTRAL

115 VAC POWER NEUTRAL

Output to Secondary Operator

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

NC

NO

12345678

12345678

DANGER

HIGH VOLTAGE!