10 Commissioning

10.5 Heating System

Check that all remote controls are calling for heat.

Allow the system to reach maximum temperature and examine
for water leaks.

The boiler should then be turned off and the system drained off
as rapidly as possible whilst still hot.

Refill the system, vent and again check for water soundness.

For sealed water systems adjust to initial design pressure. The
set pointer on the pressure gauge should be set to coincide with
the indicating pointer.

The overrun thermostat will keep the pump running when the
boiler shuts down, so long as the temperature within the boiler
is above a predetermined level.

When commissioning the system the boiler should be fired with
the bypass fully closed on full service, that is, central heating
and domestic hot water.

The system should then be balanced, adjusting the pump and
lockshield valves as necessary to achieve flow rates, refer to
Section 2.4.

Having achieved a satisfactory condition, operate the boiler
with the bypass closed on minimum load, normally central
heating only with one radiator operating in the main living area.
The valve should be opened gradually to achieve the appropriate
flow rate as quoted in Section 2.4. If necessary readjust the
pump.

Under NO circumstances should this valve be left in the FULLY
Closed position.

10.6 Condensate Check

After 30 minutes of running, turn the boiler off and remove the
inner case.

Check that there are no condensate leaks from the fan outlet/
flue elbow or fan inlet/flue hood joints. Also check for leaks from
the condensate drainage system.

10.7 Operational Checks

Adjust the control thermostat and any system controls to their
required settings and set “high/low” switch to “high”.

Do not attempt to adjust the thermostat calibration screw.

Operate the boiler again on full service and check that the
balancing is satisfactory, making further adjustments as
necessary to the system, radiator valves and bypass.

There must be no pumping over of water or entry of air at the
vent above the feed and expansion cistern.

If thermostatic radiator valves are fitted care must be taken to
make sure that there is an adequate flow rate through the boiler
and bypass when the valves are closed. For guidance on the
use of thermostatic radiator valves refer to the current issue of
BS7478 and British Gas Publication “Guidance Notes for
Installation of Domestic Condensing Boilers”.

To check the operation of the flame supervision device, with the
burner alight, turn gas service cock to “Off” the burner will go
out. There will be one attempt to relight, indicated by a 5 second
ignition phase.

Wait 30 seconds.

Turn the gas cock to “ON” and the burner should NOT relight.

Turn the control thermostat knob to “OFF” and then “ON” again
and the burner WILL now relight.

Turn “high/low” switch to “low” and observe low flame, then
return switch to “high”.

Refit the outer case, see diagram 5.2 and secure the case with
the screws from the fittings pack.

11 User Information

NOTES:

Instruct and demonstrate the efficient and safe operation of the
boiler, heating system and if fitted the domestic hot water
system.

Advise the user that, like all condensing boilers this appliance
will produce a plume of condensation from the flue terminal in
cool weather. This is due to the high efficiency and hence low
flue gas temperature of the boiler.

Show the user the position of “Lighting Instructions” - refer to
Instructions for Use.

Advise the user that for summer use the “high/low” switch can
be turned to “low”.

Advise the user of the precautions necessary to prevent damage
to the system and building in the event of the heating system
being out of use during frost and freezing conditions.

Advise the user, that to ensure the continued efficient and safe
operation of the boiler it is recommended that it is checked and
serviced at regular intervals. The frequency of servicing will
depend upon the particular installation conditions and usage,
but in general once a year should be enough.

Draw attention, if applicable, to the current issue of the Gas
Safety (Installation and Use) Regulations, Section 35, which
imposes a duty of care on all persons who let out any property
containing a gas appliance.

It is the Law that servicing is a carried out by a competent
person.

Reminder - Leave these instructions and the “Benchmark”
logbook with the user.