2 water system – Glow-worm EnergySaver 80 User Manual

Page 9

Advertising
background image

9

221837B

0246M

2 Water System

Diagram 2.3

Diagram 2.4

3 LITRES (0.66 gals)
MAKE-UP BOTTLE
(if required)

NON-RETURN
VALVE

AUTO
AIR
VENT

FLOW

DRAIN
COCK

BOILER

SAFETY
VALVE

(Make-up
alternatives)

EXPANSION
VESSEL

PRESSURE
GAUGE

CIRCULATING
PUMP

FILLING POINT

AIR
RELEASE
POINT

HEATING

CIRCUIT

22mm (min)
BY-PASS WITH
LOCKSHIELD
VALVE

RETURN

Open (vented) ststem.
Recommended
rellationship between
pump,cold feed and vent.

22mm (MIN.) VENT

FEED AND
EXPANSION
CISTERN

15mm (MINIMUM)
COLD FEED

22mm (MINIMUM) BY-
PASS WITH
LOCKSHIELD VALVE

1150mm
MIN.

BOILER

150mm

MAX

FLOW

PUMP

RET.

CYLINDER

FLOW

RET.

HEATING

450mm
MIN.
HEIGHT

2.8 Domestic Hot Water System - Unvented

Where a storage system will not have a vent to atmosphere the
installation must comply with the Building Regulations and local
Water Company bylaws, see also the current issue of BS5546
and BS6700.

If fitting to an existing system the local authority should be
informed.

2.9 Sealed Water Systems

The installation must comply with the appropriate requirements
of the current issue of BS4814, BS5449, BS6759, BS6798 and
BS7074 Part 1 and 2.

See diagram 2.4 for a suggested layout.

2.10 Safety Valve

A safety valve must be fitted to a sealed system.

It shall be preset, nonadjustable with a lift pressure of 3bar,
incorporating seating of a resilient material, a test device and a
connection for drain.

The drain from the safety valve must be routed clear of any
electrical fittings and positioned so that any discharge can be
seen.

5814