13 fault finding – Glow-worm EnergySaver 80 User Manual

Page 29

Advertising
background image

29

221837B

13 Fault Finding

Has boiler been
operating for 10

seconds yet ?

Does gas ignite ?

2

YES

NO

YES

Isolate supply

NO

Replace PCB

Examine electrode and

leads. Repair/replace

as necessary

Reconnect supply

Is APS neon lit ?

Is fan running ?

Replace APS

1

Is there 240V at the fan ?

Replace ignition

PCB

Flue hood overheating-

blocked secondary heat

exchanger (clean/replace)

Replace flue hood

thermostat

Will flue hood

thermostat reset?

- is there 240V at

the fan?

Is there 240V

at C ?

YES

YES

NO

NO

YES

NO

NO

Replace fan

Switch High/Low Switch

to 'low'

Is there a spark at

electrode ?

Can the “low” gas

pressure be set

(see data tables)

at test point on gas

valve?

YES

NO

YES

Diagram 13.1

NO

Check continuity of

both main coils

Coils ok?

Replace

ignition

PCB

Replace as

necessary

YES

NO

YES

NO

YES

NO

NO

Does gas

ignite?

Faulty injector

Replace

NO

3

YES

Does discharge tube on

ignition PCB flash ?