13 Fault Finding

Diagram 13.1

Does the burner

remain alight ?

Isolate supply

Check continuity

between 4 and 1 on

High/Low switch.

Switch ok ?

Replace

High/Low

switch

NO

YES

2

Replace gas valve

YES

NO

NO

YES

NO

NO

Turn High/Low switch to

“High”.

Check and adjust “High”

gas pressure

(see data tables)

Is gas pressure OK?

Adjust gas

pressure

Does “High” neon light ?

Is condense drain

blocked, repair.

Does burner remain

alight ?

Is the low gas pressure

setting correct (see Data

Tables) at the test point

on the gas valve ?

NO

YES

3

YES

YES

YES

NO

Boiler satisfactory

Is the low gas pressure setting

correct (see data tables)?

Adjust as necessary.

Does burner remain alight?

Will burner remain alight if gas

pressure is temporarily

increased?

NO

Faulty injector - Replace

(Reset pressure)

YES

Faulty PCB flame detection -

Replace PCB

(Reset pressure)