Installation – Desa EFS33NRB User Manual

Page 15

Advertising
background image

www.desatech.com

113132-01A

15

ON

POSITION

OFF

POSITION

2.

Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas or opening main gas valve lo-
cated on or near gas meter for natural gas, or
using compressed air.

3.

Check all joints from gas meter to equipment
shutoff valve for natural gas or propane/LP sup-
ply to equipment shutoff valve for propane/LP
(see Figures 22 and 23). Apply noncorrosive
leak detection fluid to all joints. Bubbles form-
ing show a leak.

4.

Correct all leaks at once.

CHECKING GAS CONNECTIONS

WARNING: Test all gas pip-

ing and connections, internal
and external to unit, for leaks
after installing or servicing. Cor-
rect all leaks at once.

WARNING: Never use an

open flame to check for a leak.
Apply a noncorrosive leak de-
tection fluid to all joints. Bubbles
forming show a leak. Correct all
leaks at once.

CAUTION: Make sure exter-

nal regulator has been installed
between propane/LP supply and
fireplace. See guidelines under
Connecting Fireplace to Gas
Supply, page 14.

Pressure Testing Gas Supply Piping
System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.

Disconnect fireplace with its main gas valve
(control valve) and equipment shutoff valve
from gas supply piping system. Pressures
in excess of 1/2 psig will damage fireplace
regulator.

2.

Cap off open end of gas pipe where equip-
ment shutoff valve was connected.

3.

Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas or opening main gas valve lo-
cated on or near gas meter for natural gas, or
using compressed air.

4.

Check all joints of gas supply piping system.
Apply noncorrosive leak detection fluid to all
joints. Bubbles forming show a leak.

5.

Correct all leaks at once.

6.

Reconnect fireplace and equipment shutoff
valve to gas supply. Check reconnected fit-
tings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG
(3.5 kPa)

1.

Close equipment shutoff valve (see Figure 21).

INSTALLATION

Continued

Figure 21 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff Valve

Figure 23 - Checking Gas Joints for

Propane/LP Gas

Propane/LP
Supply Tank

Figure 22 - Checking Gas Joints for

Natural Gas

Gas Control Valve

Equipment Shutoff Valve

Equipment Shutoff Valve

Gas Meter

Gas Control Valve

Pressure Testing Fireplace Gas
Connections

1.

Open equipment shutoff valve (see Figure 21).

2.

Open main gas valve located on or near gas
meter for natural gas or open propane/LP sup-
ply tank valve.