Air for combustion and ventilation, Continued, Ventilation air – Desa EFS33NRB User Manual

Page 7

Advertising
background image

www.desatech.com

113132-01A

7

Example:

Gas water heater

_____________ Btu/Hr

Vent-free fireplace

_____________ Btu/Hr

Total

_____________ Btu/Hr

4.

Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.

________ Btu/Hr (maximum the space can support)

________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space
can support)

73,000 Btu/Hr (actual amount of
Btu/Hr used)

The space in the example is a confined space because
the actual Btu/Hr used is more than the maximum
Btu/Hr the space can support. You must provide ad-
ditional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoin-

ing room. If the extra space provides an uncon-
fined space, remove door to adjoining room or add
ventilation grills between rooms. See Ventilation
Air From Inside Building.

B. Vent room directly to the outdoors. See Ventila-

tion Air From Outdoors

.

C. Install a lower Btu/Hr fireplace, if lower Btu/Hr

size makes room unconfined.

If the actual Btu/Hr used is less than the maximum
Btu/Hr the space can support, the space is an un-
confined space. You will need no additional fresh
air ventilation.

WARNING: If the area in

which the heater may be oper-
ated is smaller than that defined
as an unconfined space or if the
building is of unusually tight
construction, provide adequate
combustion and ventilation air
by one of the methods described
in the

National Fuel Gas Code,

ANSI Z223.1/NFPA 54 Section
5.3 or applicable local codes.

AIR FOR COMBUSTION

AND VENTILATION

Continued

40,000
33,000
73,000

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un-
confined space. When ventilating to an adjoining
unconfined space, you must provide two perma-
nent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting
the two spaces (see options 1 and 2, Figure 3). You
can also remove door into adjoining room (see op-
tion 3, Figure 3). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for
Combustion and Ventilation
for required size of
ventilation grills or ducts.

Figure 4 - Ventilation Air from Outdoors

Figure 3 - Ventilation Air from Inside

Building

Outlet
Air

Ventilated
Attic

Outlet
Air

Inlet
Air

Inlet Air

Ventilated

Crawl Space

To

Crawl

Space

To Attic

;;;;;;

;;;;;;

;;;;;;

;;;;;;

;;;;;;

;;;;;;

;;;;;;

QQQQQQ

QQQQQQ

QQQQQQ

QQQQQQ

QQQQQQ

QQQQQQ

QQQQQQ

;;;;

;;;;

;;;;

;;;;

QQQQ

QQQQ

QQQQ

QQQQ

;;

;;

QQ

QQ

;;;;;

;;;;;

QQQQQ

QQQQQ

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills

Into Adjoining Room,

Option 2

Ventilation

Grills

Into Adjoining

Room,

Option 1

12"

12"

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills
or ducts. You must provide two permanent open-
ings: one within 12" of the ceiling and one within
12" of the floor. Connect these items directly to
the outdoors or spaces open to the outdoors. These
spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
Section 5.3, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.

IMPORTANT:

Do not provide openings for inlet

or outlet air into attic if attic has a thermostat-con-
trolled power vent. Heated air entering the attic
will activate the power vent.

Advertising