Installation instructions, Led light, Mounting the ilb-3020 – IOTA ILB-3020-CW 24 600mA User Manual

Page 2: Wiring, Installing the charge indicator, Installing the test switch, Illustration 1 recessed troffer fixture, Illustration 2 strip fixture

Advertising
background image

Page 2

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the
ILB-3020 unit connector is disconnected.

1. LED LIGHT

The

ILB-3020 can be used with most LED light bars that operate up to 24 Watts.

2. MOUNTING THE ILB-3020

Remove the ballast channel cover. Mount the

ILB-3020 in the ballast channel at least ½

″ away from the A.C.

driver. The

ILB-3020 may also be mounted on top of the fixture. The optional top mounting kit (Catalog No. TMK-

32) may be ordered separately from Customer Service.

When battery packs are remote mounted, the remote distance can not exceed ½ of the distance from driver

to lamp specified by the A.C. driver manufacturer. Under no circumstances should the battery pack exceed a

distance of 50

′ from the lamp. The maximum allowable distance of the ILB-3020 battery from the ILB-3020 elec-

tronics is 2 feet.

3. WIRING

Refer to the wiring diagram on the back page for the appropriate wiring of LED light bar(s) and driver. Install

in accordance with the National Electrical Code and local regulations. For additional wiring diagrams consult

Customer Service.

4. INSTALLING THE CHARGE INDICATOR

Recessed Fixture – Select a convenient location with proper clearance in the ballast or access cover and drill

or punch a

7

/

8

″ hole (½″ knockout). Insert the

7

/

8

″ bushing into the hole. Push the plastic tube through the bushing.

Disconnect the leads from the

LED housing and route the leads down the plastic tube. Reconnect the leads to the

housing, observing the proper polarity (Red/Black or Red lead w/connector to positive (+) red tab). Push the entire

assembly back into the tube until the lens collar rests against the plastic tube. The plastic tube should be adjusted

so that the

Charge Indicator is within ¼

″ of the fixture lens. The Charge Indicator must be visible after installa-

tion. Refer to Illustration 1.

Strip Fixture – Select a convenient location on the side of the fixture so the

Charge Indicator can be seen after

installation. Allow for proper clearance inside the fixture and drill or punch a ½

″ hole. Disconnect the leads from

the

LED housing. Push the LED housing into the ½

″ hole until it is firmly locked in place. Reconnect the leads,

observing proper polarity (Red/Black or Red lead w/connector to positive (+) red tab). Refer to Illustration 2.

5. INSTALLING THE TEST SWITCH

The

Test Switch should be mounted on the ballast channel cover of a recessed troffer, or on the side of a strip

fixture, preferably adjacent to the

Charge Indicator. Drill or punch a ½

″ mounting hole.

7/8" BUSHING

FIXTURE

BALLAST CHANNEL COVER

PLASTIC TUBE

CHARGE INDICATOR
LIGHT

FIXTURE LENS

Illustration 1

Recessed Troffer Fixture

FIXTURE

CHARGE

INDICATOR

LIGHT

+ RED/BLK
OR RED LEAD

WHITE/RED

LEAD

+ RED

Illustration 2

Strip Fixture

ILB-3020

OBSERVE PROPER POLARITY

ILB-3020