Typical wiring diagram, For other diagrams, consult our customer service, Page 4 – IOTA ILB-3020-CW 24 600mA User Manual

Page 4

Advertising
background image

Page 4

TYPICAL WIRING DIAGRAM

For other diagrams, consult our Customer Service.

RED

RED

EMERGENCY LED

DRIVER

STANDARD LED

DRIVER

COMMON

RED/WHT

BLUE

BLK/ORG

120V (BLK)

277V (ORG)

RED OR RED BLK (+)

WHT/RED

WHITE (-)

RED

BLACK (-)

RED (+)

DO NOT MATE CONNECTOR UNTIL INSTALLATION

IS COMPLETE AND AC POWER IS SUPPLIED.

ч

ч

ш

BLK/ORG LEAD FOR COLD-WEATHER UNIT ONLY.
FOR NON-COLD WEATHER UNITS, CAP BLK/ORG LEAD.
FOR COLD-WEATHER UNIT 120V INSTALLATION, CONNECT BLK/ORG TO BLK.
FOR COLD-WEATHER UNIT 277V INSTALLATION, CAP BLK/ORG AND BLK SEPARATELY.

ø

ILB-3020 AND ILB-3020-CW

SELECT PROPER LOAD

REQUIREMENT. SINGLE WIRE

FROM STD DRV ONLY (BLUE)

UNIT

CONNECTOR

*EMERGENCY OPERATION

TEST ACCESSORY LEADS-OBSERVE PROPER

POLARITY WIRING.

ù

#1

#2

BATTERY PACKS

20W LED

ù

WHITE

TEST

SWITCH

BLACK

SWITCHED OR

UNSWITCHED LINE

20W LED

20W LED

20W LED

20W LED*

COMMON

OPTIONAL CONNECTOR FOR COLD-WEATHER
HEATING BLANKET ONLY. FOR NON-COLD-WEATHER
UNITS, LEAVE DISCONNECTED.

SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD.

UNSWITCHED LINE

RED (+)

68020-000

REV 121812