Ppendix, Uick, Hart – Labconco Fume Adsorbers 3955422 User Manual

Page 34: Dsorbers

Advertising
background image

Product Service 1-800-522-7658

30




A

PPENDIX

D

Q

UICK

C

HART

F

OR

T

HE

F

UME

A

DSORBERS








To determine the actual face velocity at the sash opening, airflow velocity readings
will need to be taken across the opening. The “average face velocity” is achieved
by taking readings in two rows across the enclosure with the readings 6" from the
ends and evenly spaced every 12"; the first row is 3" down from the upper plastic
hood canopy and the second row is 3" up from the work surface.


Model Size

30"

60"

Height from Work Surface (inches)

13.50

13.50

Total Open Area with Bypass (sq. ft.)

2.75

5.55

Exhaust Airflow Volume at 35 fpm (CFM)

100

200

*Motor Horsepower (HP)

0.05

0.10