Xi. specifications – SurgeX SX-20NE-RT-AR User Manual

Page 29

Advertising
background image

SX-20NE-RT-AR User Manual

Page 28


XI. Specifications

Physical

Model

Width

Depth

Height

Weight

SX-20NE-RT-AR

12.0”

4.0”

12.0”

14 lb.

Temperature

5 - 35° C

Humidity Range

5% to 95% R.H., non-condensing


AC

Load Rating

20 Amps @ 120 Volts (2400W)

Power Requirement (no load)

20 Watts

UL 1449 Adjunct Classification Test
Results

1000 surges, 6000 Volts, 3000 Amps,B3 pulse,
measured suppressed voltage 170 Volts, no failures

Maximum Applied Surge Pulse Joule
Rating

Unlimited, due to current limiting (8 x 20 µs)

Maximum Applied Surge Pulse
Voltage

6000 volts (1.2 x 50 µs pulse),industry standard rating

Maximum Applied Surge Pulse
Current

Unlimited, due to current limiting (8 x 20 µs)*

Endurance

IEEE C62.41-1991 Category B3 (C1)

Pulses

1 kV>500,000; 3 kV>10,000; 6 kV>1000

Maximum Load Inrush Energy

1000 Joules total during power-up

EMI/RFI
Filter

Normal Mode (50

Ω load) 40 dB@100 kHz;50 dB@300 kHz;50 dB@3 MHz;50

dB@30 MHz

Common Mode (50 Ω
load)

18 dB@300 kHz; 30 dB@1 MHz;50 dB@5 MHz; 50
dB@20 MHz


Remote Connections

Remote Control Voltage

5 – 30VDC

Remote Control Current Draw

5mA maximum

Contact Closure Max. Resistance

100 Ω

Auxiliary Relay Contact Rating

30VDC @ 1A

12V Output Max. Current

20mA


Network

Single 10/100 Unshielded Twisted Pair Ethernet Jack
IP Addressed: DHCP Assigned or Static
Internal HTTP Web Server
Forms Processing Browser Required
Internal Telnet Server

Compliance

UL/cUL

UL60950 Listed I.T.E.
File No. E225914
UL 1449 3

rd

Edition In Progress

CE

Directives 89/336/EEC, 92/31/EEC and 93/68/EEC
EN 60950: 3

rd

Edition

EN55022: 1998 Class B

FCC

Part 15 Class B

*1.2 x 50 µs pulse, industry standard combination wave surge, as per IEEE C62.41

Advertising