Ii. installation, Physical, Ethernet connection – SurgeX SX-20NE-RT-AR User Manual

Page 6: Ac power connections

Advertising
background image

SX-20NE-RT-AR User Manual

Page 5


II. Installation

Physical

The SX-20NE-RT-AR is housed in a magnetic shielding NEMA enclosure designed to be
installed at a service entrance, electrical sub-panel, or in a ceiling plenum. Input and Output AC
connections are made through the enclosure knock-outs and are hard-wired to internal terminal
blocks.

Ethernet Connection

The RJ45 connector for 10/100 Ethernet is situated on the bottom of the unit. The default IP
Address is 192.168.1.254.

AC Power Connections

Connect the wires to the equipment (load) to be powered On and Off to the lower terminal block
labeled “Load”. Connect Black to Load, White to Neutral, and Ground to Ground. If the
connected equipment has a Power switch, leave it in the On position to allow the SX-20NE-RT-
AR to control the power.

Connect the wires from the electrical service (line) to the upper terminal block labeled “Line”.
Connect Black to Line, White to Neutral, and Ground to Ground.

IMPORTANT: In order for the SurgeX circuitry to function properly, the unit must be
installed exactly as stated above (the unit will not function without a Neutral connection).
The SurgeX SX-20NE-RT-AR product is rated at a load capacity of 20 Amps and shall be
wired only by qualified Electricians using 12 Ga. conductors as specified in Article 310 of the
1999 National Electric Code, as set forth in Table 310-13. Any type of conductor suitable for
use in wet or dry locations such as (but not limited to) THHN, THHW, THW, THWN, or TW
shall be considered acceptable if local Code permits. The circuit to which the product is
connected must be protected by a 20 Amp circuit breaker.