ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL

Step 5: Provide Line Voltage Wiring

• Check unit data plate located on control side of chassis

for ampacity and fuse size.

• Remove electrical knockouts from chassis backplate.

• Run line voltage wiring through knockout and secure

wiring to backplate or disconnect.

Step 6: Chassis Installation

• Level and secure backplate to wall.

• Position the chassis against back plate. Drive (2) screws

through holes in lip of backplate into top flange of chassis.

Step 7: Final Electrical Connection

• Install flexible electrical conduit between the backplate or

electrical disconnect and the unit mounted junction box.

• Make final wiring connections in disconnect and junction

box, taking care to replace all covers when done. Wiring

must conform to NEC and/or all local codes. Refer to

Electrical Data.

NOTE: It is necessary to make final wiring connections

prior to securing unit chassis to back plate on right-hand

piping models with electrical disconnect.

Step 8: Final Water Connection

• For ease of installation and sound attenuation, high

pressure (recommended) flexible hoses with a swivel

fitting should be provided. Apply Teflon® tape or sealant

compound to threaded hose fittings.

• Combination shut-off/balancing valves should be installed

on both the supply and return water lines of the unit.

• Flow control valves should be installed on the water

discharge line.

• It is recommended that P/T ports be installed on the

supply and return water lines.

Step 9: Set Unit Controls

• Locate the “continuous fan/cycle fan” switch within the

electrical compartment of the chassis and set to desired

position. (Remote wall thermostat units do not use this

optional switch.)

• Optional Control Settings- Remote Thermostat - Run

low voltage wiring from unit to the desired thermostat

location. Mount and wire thermostat according to

manufacturer’s recommendations.

Motorized Outside Air Damper - Locate the “damper on/

damper off” damper switch within the electrical com-

partment of the chassis and set to desired position.

Step 10: Secure the Cabinet Cover

• Position and lower cabinet over unit chassis. Apply

pressure to the front of the cabinet to ensure that the

back lip of the cabinet hooks over the tabs provided on

the backplate.

• Secure cabinet to chassis with mounting screws provided.

Step 11: Perform Final Unit Check

• Measure the pressure drop across the water coil and

monitor water or air temperatures in both heating

and cooling modes. The measured values should fall

within the acceptable ranges shown in the Startup

Performance table.