Envision controls cont, Optional fx10 control – WaterFurnace Envisio Series Console User Manual

Page 30

Advertising
background image

30

ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL

Optional FX10 Control

The optional FX10 control provides unparalleled capability

in several areas including performance monitoring, zoning,

humidity, energy management, and service diagnosis, and

then communicates it all thru standard DDC protocols like

N2, Lon and BACnet (MS/TP @ 19,200 Baud rate).

The most unique feature is integrating the FX10 into the

Envision series as both the heat pump and DDC controller

providing both a cost advantage and providing features

not typically found on WLHP controls. This integration

allows heat pump monitoring sensors, status and service

diagnosis faults to be communicated thru the DDC direct

to the building automation system (BAS), giving building

supervisors detailed and accurate information on every

piece of equipment without removing an access panel.

FX10 Advanced Control Overview

The Johnson Controls FX10 board is specifically designed

for commercial heat pumps and provides control of the

entire unit as well as input ports for Open N2, LonTalk,

BACnet (MS/TP @ 19,200 Baud rate) communication

protocols as well as an input port for a user interface. The

user interface is an accessory item that can be used to aid

in diagnostics and unit setup. A 16-pin low voltage terminal

board provides terminals for common field connections. The

FX10 Control provides:

• Operational

sequencing

• High and low-pressure switch monitoring

• General

lockout

• Freeze

detection

• Condensate overflow sensing

• Lockout mode control

• Emergency shutdown mode

• Random start and short cycle protection

Short Cycle Protection

Allows a minimum compressor “off” time of four minutes

and a minimum “on” time of two minutes.

Random Start

A delay of 1 to 120 seconds is generated after each power-

up to prevent simultaneous startup of all units within a

building after the release from an unoccupied cycle or

power loss.

Emergency Shutdown

A field-applied dry contact can be used to place the control

into emergency shutdown mode. During this mode, all

outputs on the board are disabled.

Freeze Detection Limit

Field selectable for 15° or 30°F (-9° or -1°C)

Installation Options

• Standalone controlled by standard room thermostat

• Standalone with a Zone Temperature Sensor (must

have user interface to change set points beyond the

allowed +/- 5°F [2.7°C])

• Integrated into BAS by adding communication module

Accessory Outputs

Quantity 2. One cycled with blower, other with compressor.

User Interface

4 x 20 backlit LCD.

Optional Plug-in Communication Modules -
(compatible with standard BAS protocols)

• Open

N2

• LonTalk

• BACnet (MS/TP @ 19,200 Baud rate)

Display

Requires DLI Card/Kit. Up to 2 displays, either 1 local and

1 remote, or 2 remote. (A 2-display configuration requires

identical displays.) Local display can be up to 3 meters

from the controller, power supply, and data communication.

Remote display can be up to 300 meters from the

controller. Remote display must be independently powered

with data communication done via 3 pole shielded cable.

Control Timing and Fault Recognition Delays

Lead compressor “ON” delay ..........................................90 seconds

(not applicable for single compressor models)

Minimum compressor “ON” time ...................................... 2 minutes

(except for fault condition)

Short cycle delay ..................................................................... 5 minutes

Random start delay .......................................................0-120 seconds

High pressure fault ................................................................. <1 second

Low pressure fault ...............................................................30 seconds

Freeze detection fault ...........................................................30 seconds

Envision Controls cont.

Main FX 10 Board

Advertising