Operating parameters, Operating limits, Single speed models – WaterFurnace Envisio Series Console User Manual

Page 39: Envision console - 50 hz installation manual

Advertising
background image

39

ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL

Operating Parameters

Single Speed Models

Operating Limits

Operating Limits

Cooling

Heating

(°F)

(°C)

(°F)

(°C)

Air Limits
Min. Ambient Air

45

7.2

45

7.2

Rated Ambient Air

80

26.7

70

21.1

Max. Ambient Air

100

37.8

85

29.4

Min. Entering Air

50

10.0

40

4.4

Rated Entering Air db/wb

80.6/66.2

27/19

68

20.0

Max. Entering Air db/wb

110/83

43/28.3

80

26.7

Water Limits
Min. Entering Water

30

-1.1

20

-6.7

Normal Entering Water

50-110

10-43.3

30-70

-1.1

Max. Entering Water

120

48.9

90

32.2

NOTE: Minimum/maximum limits are only for start-up conditions, and
are meant for bringing the space up to occupancy temperature. Units
are not designed to operate at the minimum/maximum conditions on
a regular basis. The operating limits are dependant upon three primary
factors: 1) water temperature, 2) return air temperature, and 3) ambient
temperature. When any of the factors are at the minimum or maximum
levels, the other two factors must be at the normal level for proper and
reliable unit operation.

Entering

Water Temp

°C

Water Flow

l/s/kW

Cooling

Suction Pressure

kPa

Discharge

Pressure kPa

Superheat

Subcooling

Water Temp

Rise °C

Air Temp Drop

°C DB

10

0.1

876 - 993

1413 - 1551

3 - 6

6 - 8

10 - 12

10 - 12

2.9

827 - 965

1276 - 1413

4 - 8

3 - 6

4 - 6

10 - 12

21

0.1

958 - 1062

1931 - 2068

4 - 6

4 - 7

10 - 12

10 - 12

2.9

945 - 1048

1724 - 1862

5 - 7

4 - 6

4 - 6

10 - 12

32

0.1

986 - 1089

2482 - 2620

4 - 6

5 - 7

10 - 12

9 - 11

2.9

972 - 1076

2275 - 2413

5 - 7

4 - 7

4 - 6

9 - 11

8/17/10

Entering

Water Temp

°C

Water Flow

l/s/kW

Heating

Suction Pressure

kPa

Discharge

Pressure kPa

Superheat

Subcooling

Water Temp

Drop °C

Air Temp Rise

°C DB

10

0.1

503 - 545

1924 - 2096

4 - 7

1 - 3

4 - 6

10 - 13

2.9

545 - 586

1965 - 2137

4 - 8

1 - 3

2 - 3

11 - 14

21

0.1

710 - 752

2124 - 2296

4 - 7

2 - 4

4 - 6

11 - 14

2.9

758 - 800

2172 - 2344

5 - 7

2 - 4

2 - 4

12 - 16

32

0.1

965 - 1007

2275 - 2517

6 - 8

4 - 6

6 - 8

14 - 18

2.9

1007 - 1055

2344 - 2586

6 - 8

4 - 6

4 - 6

16 - 19

8/17/10

NOTE: Cooling performance based on entering air temperatures of 27°C DB, 19°C WB. Heating performance based on entering air
temperature of 21°C DB.

Advertising