Compressor Minimum On Delay

The compressor minimum on delay will ensure that the

compressor output is enabled for a minimum of (2)

minute each time the compressor output is enabled. This

will apply in every instance except in the event the high

pressure switch is tripped or emergency shutdown then the

compressor output will be disable immediately.

Compressor Short Cycle Delay Time

The compressor short cycle time delay will ensure

that the compressor output will not be enabled for a

minimum of (5) minutes after it is disabled. This allows

for the system refrigerant pressures to equalize after the

compressor is disabled.

Heating Cycle

On a call for heating, the blower enable output and

accessory output 2 will turn on immediately after the

random start delay timer has been satisfied. If the

compressor short cycle time delay has been satisfied,

the compressor will turn on after the blower enable and

accessory output 2 are on and the fixed compressor start

delay timers have been satisfied.

Set Point Control Mode

In set point control mode the reversing valve output

will be disabled. As the temperature drops below the

heating set point and begins to operate in the heating

proportional band, the low capacity compressor output

(BO-2) will be enabled. A PI loop in the programming

of the control will determine when the full capacity

compressor output (BO-4) is to be enabled. The

compressor must be operating in low capacity for

a minimum of 30 seconds before the full capacity

compressor output can be enabled. During low capacity

compressor operation the ECM2 blower will operate in

medium speed and will operate in high speed when the

compressor is operating at full capacity.

Thermostat Control Mode

In thermostat mode the compressor will be cycled

based on Y1 and Y2 calls from a room thermostat.

When the control receives a Y1 command (BI-7) from

the thermostat the low capacity compressor output

(BO2) will be enabled and the ECM2 blower will

operate in medium speed. When the control receives

a Y2 command (BI-8) from the thermostat the full

capacity compressor output will be enabled and the

ECM2 blower will operate in high speed. During the

heating cycle the reversing valve will be commanded

into the off position.

Cooling Cycle

On a call for cooling, the blower enable output and

accessory output 2 will turn on immediately after the

random start delay timer has been satisfied. If the

compressor short cycle time delay has been satisfied,

the compressor will turn on after the blower enable and

accessory output 2 are on and the fixed compressor start

delay timers have been satisfied.

Set Point Control Mode

In set point control mode the reversing valve output

will be enabled. As the temperature falls below the

cooling set point and begins to operate in the cooling

proportional band, the low capacity compressor output

(BO-2) will be enabled. A PI loop in the programming

of the control will determine when the full capacity

compressor output (BO-4) is to be enabled. The

compressor must be operating in low capacity for

a minimum of 30 seconds before the full capacity

compressor output can be enabled. During low capacity

compressor operation the ECM2 blower will operate in

medium speed and will operate in high speed when the

compressor is operating at full capacity.

Thermostat Control Mode

In thermostat mode the compressor will be cycled based

on Y1 and Y2 calls from a room thermostat. When the

control receives a Y1 command (BI-7) from the thermostat

the low capacity compressor output (BO2) will be

enabled and the ECM2 blower will operate in medium

speed. When the control receives a Y2 command (BI-8)

from the thermostat the full capacity compressor output

will be enabled and the ECM2 blower will operate in high

speed. During the cooling cycle the reversing valve will be

commanded into the “ON” position.

Emergency Heat/Network Enabled Output (BO5)

This output is set from the factory to enable/disable

emergency heat. If a problem occurs with the unit resulting

in the compressor being locked out in heating mode, the

control will automatically enable this output to turn on field

installed electric heat. This output is interlocked with the

blower proving input BI-6 (Blower proving sensors must

be field supplied and installed). BI-6 must be connected to

PB2 position 3 (see unit schematic) in the field if no blower

proving sensor is desired. There is a configurable parameter

available through a BAS network that must be enabled if

this output is to be commanded over the BAS network.