Envision controls cont, Sequence of operation – WaterFurnace Envisio Series Console User Manual

Page 32

Advertising
background image

32

ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL

Lockout Mode

Lockout mode can be activated by any of the following fault

signals: refrigerant system high pressure, refrigerant system

low pressure, freeze detection, and condensate overflow.

When any valid fault signal remains continuously active for

the length of its recognition delay, the controller will go

into fault retry mode, which will turn off the compressor.

After the Compressor short cycle delay, the compressor

will attempt to operate once again. If three consecutive

faults occur in 60 minutes during a single heating or cooling

demand, the unit will go into lockout mode, turning off the

compressor, enabling the alarm output, and setting the

blower back to low speed operation until the controller

is reset. If the control faults due to the low pressure input

(BI-3) being open during the pre-compressor startup check,

the control will go into lockout mode immediately, disabling

the compressor from starting and enabling the alarm output

(BO-6). The lockout condition can be reset by powering

down the controller, by a command from the BAS, or by the

holding the ESC and Return keys on the MUI for 5 seconds.

Freeze Detection Limit (AI-5)

The freeze detection limit sensor will monitor the liquid

refrigerant temperature entering the water coil in the

heating mode. If the temperature drops below the freeze

detection limit trip point for the recognition delay period,

the condition will be recognized as a fault. The freeze

detection limit trip point will be factory set for 30°F (-1°C)

and will be field selectable for 15°F (-9°C) by removing

a jumper wire on BI-5. The freeze detection limit fault

condition will be bypassed 2 minutes at normal compressor

startup, to allow the refrigeration circuit to stabilize. If the

freeze detection limit sensor becomes unreliable at any time

compressor operation will immediately be suspended until

the problem is corrected. This should be displayed as an

alarm on the BAS and the MUI. This alarm will be reported a

“Water Low Temp Limit” fault.

High Pressure (BI-11)

The high-pressure switch shall be a normally closed (NC)

switch that monitors the systems refrigerant pressure. If the

input senses the high-pressure switch is open it must disable

the compressor output immediately and count the fault. The

compressor minimum on time does not apply if the high-

pressure switch opens. The compressor will not restart until

the compressor short cycle time delay has been satisfied.

Low Pressure (BI-3)

The low-pressure switch shall be a normally closed (NC)

switch that monitors the systems refrigerant pressure. The

input shall be checked 15 seconds before compressor start

up to be sure the pressure switch is closed and then ignored

for the first 2 minutes after the compressor output (BO-2) is

enabled. If the switch is open continuously for (30) seconds

during compressor operation the compressor output (BO-2)

will be disabled. The compressor will not restart until the

compressor short cycle time delay has been satisfied.

Condensate Overflow

The condensate overflow sensing circuit will monitor

the condensate level as a resistance input to AI-3. If the

condensate water level rises resulting in the input resistance

rising above the set point for the recognition delay period,

the condition will be recognized as a fault. The condensate

will be subjected to a (30) second lockout delay which

requires that the fault be sensed for a continuous (30)

seconds before suspending unit operation.

Alarm Output (BO-6)

The alarm output will be enabled when the control is in the

lockout mode and will be disabled when the lockout is reset.

Test Mode

Raising the zone temperature input (AI-1) reading to

180–220°F [82-104°C] or by holding the ESC and down

arrow keys on the MUI for 5 seconds will put the control

into test mode. In test mode the random start delay and

the compressor fixed on delay time will both be shortened

to 5 seconds and the reversing valve will be allowed to

cycle with out shutting down the compressor. If an MUI is

connected to the control LED 8 will flash and the words

“Test Mode Enabled” will be shown on the LCD display

when the control is in test mode. Test mode will be disabled

after a power cycle, 30 minute timeout, or by holding the

ESC and Up arrow keys on the MUI.

Sequence of Operation

Power Fail Restart

When the controller is first powered up, the outputs will be

disabled for a random start delay. The delay is provided

to prevent simultaneous starting of multiple heat pumps.

Once the timer expires, the controller will operate normally.

Random Start Delay

This delay will be used after every power failure, as well as

the first time the compressor is started after the control

exits the unoccupied mode or the emergency shutdown

mode. The delay should not be less than 1 second and not

longer than 120 seconds. If the control is in test mode the

random start delay will be shortened to 5 seconds.

Compressor Fixed On Delay Time

The Compressor Fixed On Delay Time will ensure that the

compressor output (B02) is not enabled for (90) seconds

after the control receives a call to start the compressor.

This delay is adjustable from 30 – 300 seconds over a BAS

or a MUI. If the control is in test mode the Compressor

Fixed On Delay Timer will be shortened to 5 seconds.

Envision Controls cont.