Envision controls cont, Optional fx10 microprocessor and bas interface, Control and safety feature details – WaterFurnace Envisio Series Console User Manual

Page 31: S interface

Advertising
background image

31

ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL

Condensate overflow fault ...............................................30 seconds

Low pressure fault bypass ................................................... 2 minutes

Freeze detection fault bypass ............................................ 2 minutes

Optional FX10 Microprocessor
and BAS Interface

The FX10 is a microprocessor based control that not

only monitors and controls the heat pump but also can

communicate any of this information back to the building

automation system (BAS). This means that not only does

the control monitor the heat pump at the unit you can also

monitor and control many the features over the BAS. This

clearly puts the FX10 in a class of its own.

The control will enumerate all fault conditions (HP, LP, CO,

LOC, and Freeze Detection) over a BAS as well as display

them on a medium user interface (MUI). HP, LP, CO and

Freeze Detection faults can all be reset over a BAS. A

Loss Of Charge fault can not be reset or bypassed until

the problem has been corrected. A MUI is invaluable as a

service tool for the building service team.

The unit can be commanded to run by a typical heat pump

thermostat or run based on heating and cooling set points

supplied by a BAS. The control board is wired with quick

connect harnesses for easy field change out of a bad

control board. All ECM variable blower speed settings can

be changed over a BAS or with a MUI. The control has an

input programmed to enable field installed emergency

heat in the event that the compressor is locked out. This

input can also be commanded on from a BAS as needed.

An alarm history can be viewed through the MUI and will

be held in memory until the unit is power cycled. Relative

humidity can be read by a 0-5VDC humidity sensor that is

displayed over the network. If you are using an ECM blower

motor the control can enable dehumidification mode based

on a set point in the control. The dehumidification set

point itself can also be changed over a BAS or with a MUI.

Dehumidification mode can also be enabled by the BAS.

Because the FX10 is not factory configured to read CO

2

levels, contact the factory for application assistance.

The FX10 control has unused analog and digital inputs

for field installed items such as air temperature, water

temperature, CO

2

or current status switches. The control has

unused binary and PWM outputs that can be commanded

over the BAS for field use. An optional Medium User

Interface (MUI) for control setup and advanced diagnostics

is available with some mounting kits, MUIK1 - Panel mount

version and the MUIK2-Wall mount version.

Zone Sensors

There are two options for zone sensors that can be used

with the FX10 control. Both sensors use a Johnson controls

A99 positive temperature coefficient type sensor. The

TAXXJ02 has a set point adjustment now which will give

the end user a +/- 5°F [2.7°C] adjustment from the set point

as well as a push button that can be used for temporary

occupancy. The control leaves the factory set to operate

with a TAXXJ02 sensor and can be changed to read the

TAXXA01 sensor through a building automation system or

with a user interface.

Standard Features

• Anti Short Cycle

• High Pressure Protection

• Low Pressure Protection

• Freeze

Detection

• Loss Of Charge Detection

• Random

Start

• Display for diagnostics

• Reset Lockout at disconnect or through BAS

• 2 Accessory outputs

• Optional BAS add-on controls

DDC Operation and Connection

Other optional network protocol boards that can be added

to the FX10 are:

• Johnson Control N2

• LonWorks

• BACnet

- MS/TP @ 19,200 Baud rate

- Limit devices to 30 on a single trunk line.

Control and Safety Feature Details

Emergency Shutdown

The emergency shutdown mode can be activated by a

command from a facility management system or a closed

contact on BI-2. The default state for the emergency

shutdown data point is off. When the emergency shutdown

mode is activated, all outputs will be turned off immediately

and will remain off until the emergency shutdown mode is

de-activated. The first time the compressor starts after the

emergency shutdown mode has been de-activated, there

will be a random start delay present.

Envision Controls cont.

S Interface

Advertising